nrgSMART
nrgSMART
™
™
Controller Confi guration Guide
Controller Confi guration Guide
POWER ::
POWER ::
User Guide
User Guide
Panels Tab :: Circuit Confi guration > Circuit Settings > Current Sensors Screen
Ref.
Field
Type
Value
Description
12
Lower Warning (column)
Input
Drop down
Menu
Lower Warning is a user defi ned threshold that indicates a lower than
expected value.
The number below the percentage setting displays the current value that
the circuit will be at if the lower warning threshold is reached.
Default is:
0%
and current value is
0.00 A
NOTE: The Use Global Threshold checkbox must be unchecked to
change a value.
From the Lower Warning drop down menu, select a percentage of the
fuse rating to indicate the lower warning sensor threshold. Select from
0% to 100% in 5% increments
.
13
Current Value (column)
Read Only
Text
Measured value.
14
Upper Warning (column)
Select
Drop down
Menu
Upper Warning is a user defi ned threshold that indicates a higher than
expected value.
The number below the percentage setting displays the current value that
the circuit will be at if the upper warning threshold is reached.
Default is:
60%
and current value is
12.00 A of 20 AMP
NOTE: The Use Global Threshold checkbox must be unchecked to
change a value.
From the Upper Warning drop down menu, select a percentage of the
fuse rating to indicate the upper warning sensor threshold. Select from
0% to 100% in 5% increments
.
15
Upper Critical (column)
Select
Drop down
Menu
Upper Critical is a user defi ned threshold that indicates a much higher
than expected value.
The number below the percentage setting displays the current value that
the circuit will be at if the upper critical threshold is reached.
Default is:
80%
and current value is
16.00 A of 20 AMP
NOTE: The Use Global Threshold checkbox must be unchecked to
change a value.
From the Upper Critical drop down menu, select a percentage of the fuse
rating to indicate the upper critical sensor threshold. Select from
0% to
100% in 5% increments
.
16
Alarm
Read Only
Light
Indicates the most elevated status of the selected sensors at the
selected location according to global threshold values (shown in this
screen).
This light indicates the breaker and threshold alarm status for the
individual circuit.
Green
: Normal current.
Yellow
: Warning threshold reached.
Orange
: Critical threshold reached.
Red
: A blown fuse or tripped breaker.
Gray
: Not connected.