Panels Tab :: Circuit Confi guration Screen
Ref.
Field
Type
Value
Description
1
Advanced
Select
Button
Allows individual circuit setting alarms to be viewed or modifi ed.
Select the
Advanced
button to open the
Circuit Settings Screen.
For information on Circuit Settings, see table
Panels Tab :: Circuit
Confi guration > Circuit Settings Screen.
2
A/B Linked
Select
Checkbox
Links and unlinks Feed A with Feed B.
When linked, values assigned to a fuse in one Feed are also assigned
to the fuse in the corresponding position in the other Feed. For example,
values assigned to the fuse in circuit location BT1A are also assigned to
the fuse in circuit location BT1B. If the Fuse/CB rating is 50 in BT1A and
is changed to 40, it will also be changed in BT1B. The same is true if the
setting is changed in BT1B it will change in BT1A. They both refl ect the
same settings when linked.
NOTE: Alarm threshold states remain independent even when linked
is selected and display the fuse status for the fuse in the row it is
located on.
When unlinked, the values assigned to a fuse in one Feed can be
confi gured to different values from the other Feed. Both Feeds are
independent of each other when unlinked.
To link Feed A to Feed B,
select
(to check) the
A/B Linked
Checkbox. To
unlink the Feeds,
deselect
the Checkbox.
NOTE: The following fi elds are column headings that defi ne data displayed in rows within the columns.
3
Circuit (column)
Read Only
Text
Indicates the fuse type and its location in the panel.
Circuit outputs can include:
nrgNET, BTx, GMT, TPS and TLS.
Refer to 6.2,
Fuse/Circuit Breaker Ratings for more information.
NOTE: BDFB panels distribute power to monitor the alarm card
through the nrgNET bus for controller communication. When applicable,
the nrgNET power data displays on the fi rst row in the Circuit
Confi guration Screen.
Figure 25 - Circuit Confi guration Screen
1
5
4
3
6
7
8
2