Controller Confi guration Guide
Controller Confi guration Guide
POWER ::
POWER ::
User Guide
User Guide
Panels Tab :: Circuit Confi guration Screen
Ref.
Field
Type
Value
Description
4
Bullet Terminal Option
(column)
Select
Button and
Drop down
menu
Identifi es the bullet terminal on the circuit in the selected row.
Bullet terminals are present and active when the panel supports
bullet terminals.
Select the
Arrow
button to open the Bullet Terminal Option drop down
menu. When the panel supports bullet terminals select from:
Single-pole
CB, Double-pole CB, Triple-pole
or
TFD
.
Not applicable when panels do not have bullet terminals present:
N/A
Refer to
6.2, Fuse/Circuit Breaker Ratings for more information.
5
Fuse/CB Rating (column)
Select
Button and
Drop down
menu
Indicates the rating for the fuse or circuit breaker installed in the panel.
To add or modify the Fuse/CB Rating, select the
Arrow
button to open
the Fuse/CB Rating drop down menu, and select from:
No Rating:
None
Fuse/CB ratings:
amperage
Refer to 6.2,
Fuse/Circuit Breaker Ratings for more information.
6
To Equipment :: Input
(column)
Read Only
Text
Displays equipment input label receiving power from the fuse located in
this row. The equipment input label is defi ned in the
Equipment Tab.
7
Current (column)
Read Only
Text
Indicates the measured amount of current going into the equipment.
Displays as amperage.
8
Status (column)
Read Only
Light
This light indicates the threshold level of current to the circuit on the row.
Green
: Normal current.
Yellow
: Warning threshold reached.
Orange
: Critical threshold reached.
Red
: A blown fuse or tripped breaker.
Gray
: Not connected.