2-point calibration settings
1.
Select ‘1st point cal’ in the receiver menu.
2.
Select the cluster to be calibrated, e.g. ‘1’.
3.
Connect a known load to the hook (we recommend no load
(zero weight), for the 1st point).
4.
Enter the weight of the 1st known load in the receiver menu.
5.
Select ‘2nd point cal’ in the receiver menu.
6.
Select the same cluster, in this case ‘1’.
7.
Connect a 2nd known load to the hook (we recommend 80-
100% of the maximum load. TIP! Pick calibration points that
differ as much as possible from one another for the best
result).
8.
Enter the weight of the 2nd known load in the receiver menu.
System reset
Make a system reset to return to default values:
1.
WITHIN 5 SECONDS FROM STARTING THE D8-1:
Press the D8-1 Select button.
The green Power-LED lights.
2.
Keep the D8-1 Select button pressed for at least 5 seconds.
The green Power-LED goes out.