relay(s) that you want to block when the overweight
warning limit (e.g. 1000 kg.) is reached.
5.
To activate a relay(s)/an indication relay(s) when the over
weight warning limit (e.g. 1000 kg.) is reached, select
WARNINGWEIGHTHIGH_OR_RELAYS. Check the relay(s)
that you want to activate when the overweight warning limit
(e.g. 1000 kg.) is reached.
Underweight settings
Set the lower alarm limit
1.
Connect the receiver to the PC program Settings Manager.
2.
Go to section 4 for cluster 1, section 5 for cluster 2, section 6
for cluster 3 or section 7 for cluster 4.
3.
Select MINWEIGHTLOW_LIMIT.
4.
Define the minimum weight, e.g. ‘25’ for 25 kg.
5.
To block a relay(s) from activating when the weight equals
or falls below the minimum weight limit (e.g. 25 kg.), select
MINWEIGHTLOW_AND_RELAYS. Uncheck the relay(s) that
you want to block when the minimum weight limit (e.g. 25 kg.)
is reached.
6.
To activate a relay(s)/an indication relay(s) when the weight
equals or falls below the minimum weight limit, select
MINWEIGHTLOW_OR_RELAYS. Check the relay(s) that you
want to activate when the minimum weight limit (e.g. 25 kg.) is
reached.
7.
To set a hysteresis value*, select WEIGHTLOW_HYSTERESIS.
Define the value: e.g. ‘50’.
Set a underweight warning limit
1.
If you need an underweight warning, select
WARNINGWEIGHTLOW_LIMIT.
2.
Define the underweight warning limit, e.g. ‘100’ for 100 kg.
3.
To block a relay(s) from activating when the weight equals
or falls below the underweight warning weight limit (e.g.
100 kg), select WARNINGWEIGHTLOW_AND_RELAYS.