Energy 4000 B / 4000 GAS
Vers. 013
GB
16
Reason:
50 hours have gone by since oil was last
changed, and you must check its level.
How to turn it off:
once you have checked the level,
press the partial counter push-button (fig. 21 ref. 9).
Keep it pressed, then turn the panel on and release the
push-button when the unit has started up.
Alarm: the red maintenance lamp is lighted.
Reason: 100 hours have gone by since oil was changed.
The oil must be replaced.
How to turn it off:Once you have changed the oil, turn
the panel on and make sure the generating set is running.
Now press the push-button hidden under the bottom right
(fig. 21 rif. 10), then release it at once. wait two minutes
before turning the unit off.
Under special conditions, the data contained in
the micropocessor inside the panel can undergo
alterations. This may be because the battery is
very low, or because the cables used to connect
the battery to the unit have too small a cross-
section. In this case, the alteration of the data
may prevent the unit from running. In order to
make the unit work again properly, proceed as
follows:
Alarm: meaningless characters appear on the display.
Reason: malfunction due to low voltage during start-up
(battery very low, cable cross-section too small).
Reinitialise the panel.
How to turn it off: press the hidden push-button; keep it
pressed while turning on the panel. Release the push-
button when 4 zeros (0000) appear on the panel The
panel has been reinitialised.
7 MAINTENANCE INSTRUCTIONS
Use only original spare
parts. T he use of spare parts of non-
equivalent quality may damage the
generating set.
Routine control and adjustments are of the
essence in preserving a high level of
performance. Routine maintenance also
ensures long generating set life.
Before performing any
check or maintenance operation on the
generating set, turn the selector switch (Fig.
22 ref. 2) to the position 1 “manual” in order
to avoid accidentally starting the generating
set up.
7.1 Maintenance list
See table at the bottom of the page.
7.2 Maintenance not requiring specialised
personnel
To perform this kind of operation, it will be
necessary to open the door of the generating set.
The following precautions must therefore be
taken:
1) The generating set must not be running, and
all its parts must be cold
2) Let the generating set cool off.
3) Turn the selector switch to the position “1”
(manual) (Fig. 22 ref. 2)
N.B. Remember to put the selector switch
back at "0" (automatic) when you have
finished the operation.
7.3 Checking the engine oil level
ROUTINE MAINTENANCE SCHEDULE
To be performed after the period of time or the number of
running hours listed here, whichever the earlier may be.
Every use
Every
month or
20 h
Every 6
month or
100 h
Every year
or 300 h
Inspection
●
Engine oil
Change
●
(2)
●
(2)
Air filter
Cleaning
(1)
●
(2)
Spark plug
Inspection-cleaning
●
(2)
Valve adjustment
Check-adjust
●
(2)
Tank and fuel filter.
Cleaning
●
(2)
Engine r.p.m.’s or frequency
Adjust
●
(2)
Vibration damper suspension points
Check
●
(2)
Fuel pipes
Check (replace if
necessary)
Ogni due anni
NOTES: (1) Clean more frequently if you use it in a very dusty environment.
(2) These operations must be performed by specialised personnel only