Control Settings

The ECON CONFIG menu includes the following control 
parameters:-

1.  MANUAL / AUTO  -- Allows the control output to be set 

to Auto or Manual control, manual control is shown 
as 0-100% and can be adjusted using the + / - buttons. 
In Auto control the output will automatically adjust to 
maintain the velocity set point.

2.  HIGH SET POINT -- This is used to enter the required face 

velocity set point for standard VAV control or the High 
set point for dual set point occupancy control.

3.  LOW SET POINT -- This is used to enter the required 

reduced face velocity set point for dual set point 
occupancy control.

4.  DAMPER / INVERTER -- This is used to set the output 

to 0-10v (direct - for damper) or 10 to 0v (reverse - for 
Inverter)

5.  MIN OUTPUT -- This is used to set the MIN output 

volume when pushbutton III is set to Min/Run/Max 
operation.

6.  MAX OUTPUT -- This is used to set the MAX output 

volume when pushbutton III is set to Min/Run/Max 
operation.

7.  LOW LIMIT -- This is used to set the fume cupboard 

minimum volume when the sash is closed (limits the 
damper closed position).

8.  HIGH LIMIT -- This is used to set the fume cupboard 

maximum volume (limits how far the damper opens).

9.  OUTPUT RANGE -- This is used to set the output range to 

0-10v (Inverter) or 2-10v (actuator).

10.  PROP BAND -- This is the main control parameter 

for the VAV control output. If the value is too low the 
damper will be unstable and hunt, if the value is too low 
the damper will react too slowly. The ideal setting for 
this value is to select a value that is as small as possible 
but that gives stable control of the damper or Inverter 
without ‘hunting’.

11.  INTEGRAL TIME -- The Integral Time is the corrective 

action of the control output. The PROP BAND control 
will result in an offset from the set point, the Integral 
will correct the error in small steps over time. The ideal 
setting is to select the highest possible value that gives 
stable control.

12.  INTERAL CUT OFF -- This is a unique parameter that is 

used to give a rapid response in control output when 
the sash is raised to boost the speed of the output. 
The parameter monitors the rate of change of the face 
velocity. This parameter should not require changing 
from the factory default setting.

13.  BOOST DURATION -- The BOOST DURATION is used in 

conjunction with a sash position sensor for VAV control. 
The controller will drive the output to a pre-determined 
position for a brief periof of time before switching back 
to face velocity control.