Instruction Manual
Tek-Bar 3800XP
www.tek-trol.com
Technology Solutions
19
4.9.6
Bluetooth Operation
Fig 15: Bluetooth Operation JP2 and JP3
Table 12: Bluetooth Pin Description
JP2
OFF
Factory Default - Self Run Mode
ON
Bluetooth Disable (Must Power Cycle after Jumper set)
JP3
ON
OTA (Over the Air Mode) - Factory Default Mode
OFF
Manufacturing Use Only
4.9.7
HART Communication
Fig 16: HART connection for the 4-20mA current loop
•
The 4 to 20mA output represents the digital Primary Variable [PV].
•
The primary variable can be setup for Differential Pressure, Static Pressure or Line
Temperature, for Tek-Bar 3800XP Multivariable Transmitter.
•
By default, the 4-20mA output is set for Differential Pressure with a Range of 0 to 100” H
2
O.
•
This can be modified to suit customer requirements using a HART master such as a 475 HHT
or AMS PC based system.
•
The 4-20mA output can have a damping value applied to smooth out any sudden changes on
the current loop, if required.
•
Damping is entered as an integer representing seconds.
+
+
+
249 Ohms
24 VDC
475
Volt
Meter
[1-5VDC]
RS232