Instruction Manual
Tek-Bar 3800XP
www.tek-trol.com
Technology Solutions
8
3
Installation
This section covers instructions on installation and commissioning. Installation of the device must
be carried out by trained; qualified specialists authorized to perform such works.
CAUTION
•
When removing the instrument from hazardous processes, avoid direct contact with
the fluid and the MVT wetted parts unless wearing PPE suitable for the environment.
•
All installations must comply with local installation requirements and local electrical
code.
WARNING
•
This section offers instructions for installation, wiring, operation, and
troubleshooting. The user must read this manual carefully before installation and
operation because improper installation may cause incorrect measurement and even
damage the Transmitter.
NOTE
•
Improper installation has the potential to cause injury and to damage instrument.
•
Periodically inspect the power cables, transducer cables, cable glands and the
enclosure for signs of damage. Inspect transducer installation and mounting hardware
for loose connections.
3.1
General Instructions
•
Installation should be according to ANSI/ISA RP 12.6 and the NEC ANSI/NFPA 70, or Canadian
Electrical Code Part 1.
•
All wiring requires a minimum of 85°C insulation rating.
•
Approved conduit seals should be installed within 18 ¼” (457mm) of the housing.
•
Equipment must be installed by qualified personnel.
•
Do not disconnect equipment unless power has been turned off or the area is known to be
non-hazardous.
•
Service connections can be used when the atmosphere is known to be safe and non-
hazardous.
•
Open enclosure when the location is known to be non-hazardous and remove power from the
meter to perform servicing.