7
LUMINAIRE CLASSIFICATION LABEL
Emergency lighting luminaires shall be classified and marked as to their construction as
follows.
A unique designation denoting the type, mode of operation, the facilities included and the
rated duration of the luminaire shall be clearly affixed to the luminaire.
The designation consists of a rectangle divided the three or four segments each containing
one or more positions. Relevant to the construction a position will obtain a letter or a figure, or
a point if no has to be given. The shape of the emergency lighting luminaire designation as
follows:
The segments and positions have to be completed by letters and figures indicating the
intended constructions.
a) First segment containing one position: TYPE
X
self-contained
Z
central supply
b) Second segment containing one position: MODE OF OPERATION
0
non-maintained
1
maintained
2
combined non-maintained
3
combined maintained
4
compound non-maintained
5
compound maintained
6
satellite
c)
Third segment containing four positions: FACILITIES. To be completed where appropriate
at the time of installation.
A
including test device
B
including remote rest mode
C
including inhibiting mode
D
high-risk task-area luminaire
d) Fourth segment containing three positions:
FOR SELF-CONTAINED LUMINAIRES to indicate the minimum DURATION of the
emergency mode expressed in minutes:
*10 to indicate
10 min duration
*60
1 h duration
120
2 h duration
180
3 h duration