3
INSTALLATION AND MAINTENANCE MANUAL FOR THE
EMERGENCY LUMINAIRE TYPES TWT22XX(X)
Product Description
Luminaire
is maintained or non-maintained emergency luminaire.
Usage targets
:
Facilities, cruise ships and other locations where emergency lighting is
required.
Points to note
Installation of this product must be done only by a qualified electrician
Only original spare parts may be used for this product. Any modifications to this product are
prohibited without manufacturer’s written permission. This product may only be used for
manufacturer’s specified use.
Technical Data
- insulation class: 2 (230V types)
- insulation class: 0 (24V types)
- casing: IP44
- applied European Directives and standards: 89/336EEC, 92/31/EEC EMC-directive,
73/23/EEC, 93/68/EEC LVD-directive, EN 55015, EN 61547, EN 60598-2-22, EN 60598-1,
EN1838
LVD-directive only for the types with 230V supply voltage.
-Type code ending to -K or -T:
The type is compatible with the Teknoware central battery
unit with automatic addressable testing. Moreover, the T- types are non-maintained luminaires
compatible with the Teknoware central battery units and Teknoware Local Controller
TS9069x.
TWT2221:
- supply voltage: 24 V AC/DC (Note! Luminaire shall be connected to 24V AC/DC emergency
lighting central battery unit)
-light source: Fluorescent lamp 9W TC-E
TWT2224:
- supply voltage: 24 V AC/DC (Note! Luminaire shall be connected to 24V AC/DC emergency
lighting central battery unit)
-light source: Fluorescent lamp 18W TC-E
TWT2281(K):
- supply voltage: 230 V AC/DC (Note! Luminaire shall be connected to 230V AC/DC
emergency lighting central battery unit)
- light source: Fluorescent lamp 9W TC-E
- lumen output: 240lm
TWT2282:
- supply voltage: 230 VAC (normal mains supply)
- self-contained luminaire with 1h battery mode duration
- light source: fluorescent lamp 9W TC-E
TWT2283:
- supply voltage: 230 VAC (normal mains supply)
- self-contained luminaire with 3h battery mode duration
- light source: fluorescent lamp 9W TC-E
TWT2284:
- supply voltage: 230 V AC/DC (Note! Luminaire shall be connected to 230V AC/DC
emergency lighting central battery unit)
-light source: Fluorescent lamp 18W TC-E