5.5
Heating
The Heating submenu offers a number of options if the device is fitted with an electronic control
system for the air discharge temperature.
The configuration parameters marked with a can only be set by a specialist technician and are
password protected.
AIR DISCHARGE TEMPERATURE SET POINT HEATING
Enter the desired air discharge temperature in °C using and , and save using .
We recommend an air discharge temperature of 32°C-37°C.
ACTIVATE SWITCH TO ROOM TEMPERATURE
The installed control valve is activated so that the set air discharge temperature is corrected
differently according to the room temperature. If the room temperature is below the set point,
the air discharge temperature is raised; if the room temperature is higher than the set point, the
air discharge temperature is reduced.
ROOM SET POINT
Set a specified temperature for the room temperature.
MAXIMUM DELTA AIR DISCHARGE TEMPERATURE
Maximum difference in air discharge temperature between the actual and set point status.
5.6
Switch test
The switch test submenu is only available to the specialist technician.
TEST FUNCTION FOR VARIOUS SYSTEM PARAMETERS
Using the switch test, outputs of the master controllers can be selected and activated individually
at the technician level. This enables troubleshooting to be localised and faulty wiring identified
easily on site.
As soon as the
menu has been selected, all connected air curtain units are set to the “OFF” mode,
and remain in this mode until completion of the switch test to prevent an uncontrolled start-up.