Page 16
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
MTU-to-ECC Communication via Ethernet
Following are steps for setting up MTU - ECC Communication through the Ethernet port via HTTP post
(not using PLC - Power Line Carrier), and NOT connecting the ECC to the Local Area Network.
(Instructions for MTU Ethernet setup when accessing the ECC on the Local Area Network are located
in separate Instructions.)
The ECC and MTU can communicate by connecting the two devices together with an Ethernet cable, or
connecting both devices to an Ethernet switch/hub (not router). See the following steps for the proper
configuration and setup.
1. Set the computer’s IP to 192.168.7.1
See the steps starting on page 35 of the TED 5000 User’s Manual for instructions on setting your
computer’s IP to a specific IP.
* Note – depending on the computer, you may need an Ethernet Crossover cable when directly con-
necting the ECC and/or MTU to the computer
2. Once the computer is set to 7.1, connect the MTU to an Ethernet switch (or directly to the computer)
– you will also have the ECC and the computer connected to this switch via Ethernet as well (if a
switch is available – if not, you can connect the MTU to the computer, set it up, and then connect it
to the ECC after setup).
3. With the MTU connected directly to the computer, (or to a switch with the computer also connected to
the switch) open your web browser and type in “http://192.168.7.3” to access the MTU setup page.
*Note –If you connect the ECC or MTU directly to the computer with the computer set to 192.168.7.1,
and you are unable to bring up the software setup (and unable to ping the IP address of 192.168.7.3
or 192.168.7.4), you will instead need to use an Ethernet ‘Crossover Cable.’ This will be more com-
mon with computers that were manufactured prior to 2011.
For more information on the ‘Crossover Cable,’ please see:
http://en.wikipedia.org/wiki/Ethernet_crossover_cable
Crossover Cables are readily available at RadioShack, WalMart, BestBuy, etc.
4. Once the MTU setup page loads, select your correct phase type from the drop-down list at the top
of the page.
5. Check the box for ‘HTTP.’ With this box checked, you can then enter in your ECC default IP, which is
192.168.7.4. Once this is entered, select SAVE at the bottom of the setup. At this point, the portion
of setting up the MTU-to-ECC direct communication is complete. To view the real time readings per
phase directly from the MTU, type: “http://192.168.7.3/stats.htm” into the browser address bar. Next
will be the ECC.
6. You can connect the ECC either directly to your computer via Ethernet, or you can run it through an Eth-
ernet switch or hub (with the computer connected to the same switch/hub via Ethernet). Once connect-
ed, open your web browser and type in “http://192.168.7.4” to bring up the Footprints live dashboard.
Select EDIT > SYSTEM SETTINGS WIZARD > go to the Product ID tab. Verify that the MTU ID entered
netzerotools.com
netzerotools.com
Содержание Pro Commercial
Страница 19: ...Page 19 Rev 1 0 13 Appendix A 1 AUTHORITY MTU HV netzerotools com netzerotools com...
Страница 20: ...Page 20 Appendix A 2 Tie White Wire to Neutral Bus MTU HV netzerotools com netzerotools com...
Страница 21: ...Page 21 Rev 1 0 13 Appendix A 3 MTU HV netzerotools com netzerotools com...
Страница 22: ...Page 22 Appendix A 4 MTU HV netzerotools com netzerotools com...
Страница 24: ...ENERGY INC netzerotools com netzerotools com...