B) Install one CT over each incoming power line A, B or C, by pressing on the handle to open the split-

core then clipping it over the power line as shown below. 

C

) The CTs should be installed on the secondary side of the main switch or main circuit breaker, how-

ever, if this is not possible, such as in the case of a combination breaker panel, then install on the
primary side of the main breaker.

D) Make sure the thumb-squeeze split core CTs clamp tightly.  (The CTs should be loose-fitting around

the wires).

E) The CT inputs on the MTU-HV are left-to-right: Phase A, Phase B, Phase C and must be matched

to the corresponding conductors for proper readings.  Important, if phasing is not correct, the device
will not measure current, power and energy correctly.

NOTE:

 The connectors are polarized and can only be inserted one way – do not force.

NOTE:

  If installed on a 208Y/120V 1-PH 3-W system, only install two of the CTs and connect to the two 

applicable ports on the MTU. The third CT is not used.

NOTE: 

While the TED Pro Commercial MTU is designed to work on services of 400A, it is possible to 

use it on services with up to three 400A parallel conductors per phase (up to 1200A) by follow-
ing these steps:

Precision Measurement of Parallel Conductors:

1. Purchase and install 1 - CT  Harness  Kit (Model ADP) and 3 additional CTs (Model CT301B) for each

additional parallel conductor. IE: If you have a 1200A service with 3 parallel conductors per phase you 
will need to purchase 1 - Model ADP harness kits and 6 additional Model CT301B CTs.

2. Refer to installation instructions provided with the CT Harness for correct installation.

F) Determine the best location to mount the MTU.

i. Choose location where it will not interfere with existing equipment or wiring.
ii. If installed in the panel, the MTU may be attached using double-sided tape (if allowed in your

jurisdiction), or with sheet metal or machine screws.

iii. If installed outside the panel, it may be mounted directly to the wall using the mounting lugs on

the MTU, or it may be mounted in a suitably sized junction box.

G) Arrange and tie-wrap all wiring in a neat and tidy manner.
H) Turn the power back on.

The MTU will blink approximately 10 times when power is first applied.  After this, it will blink when 
transmitting or receiving data. 

Do not close the electrical panel until you have completed the installation of the ECC and verified that 

Press

Here

netzerotools.com

netzerotools.com

Содержание Pro Commercial

Страница 1: ...or TED Pro CT Clamps Commercial Energy Monitor TED Pro WD Wireless Display for Commercial Energy Monitor TED Pro MTU HV Commercial Energy Monitor TED Pro MTU HV Commercial Energy Monitor TED Pro ECC C...

Страница 2: ...lation Page 18 Appendix A1 Page 19 Appendix A2 Page 20 Appendix A3 Page 21 Appendix A4 Page 22 Appendix A5 Page 23 PART I PART II PART III PART IV Appendix IMPORTANT The installation of your TED Pro s...

Страница 3: ...use multiple MTUs If your main service circuit conductors wires are larger than 1 25 inch diameter TED WILL NOT work Other TED models and accessories may be available for these applications Please se...

Страница 4: ...panel and Ethernet communication method must be used The MTU and ECC will need to be connected to the Local Area Network or connected to each other via Ethernet 2 Services with 400A parallel feeds wil...

Страница 5: ...3W Single Phase service derived from 3 Phase system North America 240 120V 1PH 3W North America 230V 1PH 2W Europe and most other countries in the world TED Pro Commercial MTU HV will not work on 120...

Страница 6: ...as are This symbol will be found throughout the instructions where there is a po tential for electric shock burn or even electrocution Do not attempt to com plete the noted section if you are not an e...

Страница 7: ...re are two or more main circuit breaker panels you will need one additional MTU for each main circuit breaker or panel For services with Wind Solar or Standby Generator an additional MTU will be requi...

Страница 8: ...MAX 1200A White neutral Black phase A Neutral Bus 15 20 or 30A Circuit Breaker CT s Main Circuit Breaker MAX 1200A A B C A B C A B A B C A B C A B Red phase B Phase B Blue phase C MTU Measuring Trans...

Страница 9: ...ral Black phase A Neutral Bus 15 20 or 30A Circuit Breaker CT s Main Circuit Breaker MAX 1200A A B C A B C A B A B C A B C A B Red phase B Phase B Blue phase C MTU Measuring Transmitting Unit Ethernet...

Страница 10: ...fluorescent lighting with noisy ballasts etc NOTE It is HIGHLY recommended that all MTU installations be made outside of the panel for ease of performing future firmware updates ease of ac cess withou...

Страница 11: ...nd NOTE 2 For optimal PLC Communication the ECC should be plugged into a circuit on the same phase as the black wire on the MTU power cable If the ECC cannot be connected to phase A the black MTU wire...

Страница 12: ...up to three 400A parallel conductors per phase up to 1200A by follow ing these steps Precision Measurement of Parallel Conductors 1 Purchase and install 1 CT Harness Kit Model ADP and 3 additional CT...

Страница 13: ...IMPORTANT THAT THE INSTALLING ELECTRICIAN VERIFY CORRECT OPERATION AND MEASUREMENT PRIOR TO LEAVING THE SITE ECC CONNECTION Select an electrical outlet free of other connections and connect ECC power...

Страница 14: ...ed instructions on installing the ECC NOTE For an Ethernet connected MTU Connect the ECC per above refer to TED Installation Utility on Page 18 item 1 Once the utility has located the TED Pro Commerci...

Страница 15: ...INSIDE Panel ECC PLC Power Line Carrier MTU HV mounted OUTSIDE Panel ECC Ethernet directly to ECC MTU HV mounted OUTSIDE Panel ECC Ethernet to Hub to ECC MTU HV mounted OUTSIDE Panel ECC Ethernet to...

Страница 16: ...and type in http 192 168 7 3 to access the MTU setup page Note If you connect the ECC or MTU directly to the computer with the computer set to 192 168 7 1 and you are unable to bring up the software...

Страница 17: ...HTTP box and enter in the ECC IP that is listed on the utility Shown on the utility as TED 6000 This completes the setup for the MTU 3000 To view the real time readings per phase directly from the MT...

Страница 18: ...ine it may say TED6000 select launch in browser NOTE After you have selected Launch in Browser you will see a grey screen and Loading should appear followed by the Footprints dashboard If your compute...

Страница 19: ...Page 19 Rev 1 0 13 Appendix A 1 AUTHORITY MTU HV netzerotools com netzerotools com...

Страница 20: ...Page 20 Appendix A 2 Tie White Wire to Neutral Bus MTU HV netzerotools com netzerotools com...

Страница 21: ...Page 21 Rev 1 0 13 Appendix A 3 MTU HV netzerotools com netzerotools com...

Страница 22: ...Page 22 Appendix A 4 MTU HV netzerotools com netzerotools com...

Страница 23: ...Page 23 Rev 1 0 13 Appendix A 5 A A PLC Signal BLACK WIRE ON THE MTU AND GW MTU HV netzerotools com netzerotools com...

Страница 24: ...ENERGY INC netzerotools com netzerotools com...

Отзывы: