20
SERVICE HANDBOOK
Table 3-3: Facts About Thermal Protectors
External Line-Break Thermal Protectors
• Currently used on all AE, AK, AZ, TP, TH, TW, HG, RK, RG, RN, and AJ models.
• Sense motor current and housing temperature or combination thereof
• Break line current when tripped
• Generally do not protect against loss of charge
• When, by design, no air flow passes over housing, a special “static” thermal protector
must be used
• Are designed for specific compressors and their intended application. Make no substitutions
• Will not protect motor if compressor is operated outside its evaporator temperature range
Internal Line-Break Thermal Protectors
• Currently used on all AH, AB, AV, AG, AW, VS and most AN, SA and SF models
• Sense motor current and motor winding temperature or combination thereof
• Break line current when tripped
• Generally protect against loss of charge
• Will not protect motor if compressor if operated outside its evaporator temperature range
• Not repairable or replaceable
Line Voltage-Electronic Protection Module (note - for more specific details consult an authorized
wholesaler)
• Originally used on some AN and SF models
• Employs use of solid state temperature sensors in motor windings and compressor
discharge muffler
• Sensor resistance values change with temperature variations
• Module will interrupt power to the contactor coil when resistance values of sensors exceed
the specified range. This power interruption thus stops the compressor motor
• Module provides protection against
– Abnormal locked rotor conditions
– Loss of refrigerant
– High compressor discharge temperatures
– Excessive current conditions
– Time delays of 3 to 5 minutes occur on power interruption or sensor trip
Internal Thermal Protectors
Internal thermal protectors are completely internal and tamper-proof. They cannot be bypassed.
Single-phase Motor Thermal Protectors
Internal thermal protectors detect excess heat and/or current draw. They are located in the fol-
lowing single-phase motors: AB, AW, AN, AH, AV, AG, and VS.
Three-phase Motor Thermal Protectors
The 31HM, 32HM, 34HM and 35HM on-winding motor protectors are 3-phase line break, au-
tomatic reset devices wired in series with each phase at the neutral point and mounted on the
windings. They are used in AB, AW, AN, AG, AV and VS models.
Содержание AH5540E
Страница 1: ...Hermetic Compressor Service Handbook Wholesale Distribution North America...
Страница 2: ......
Страница 3: ...Hermetic Compressor Service Handbook Ann Arbor MI 48108 REV 3 11...
Страница 4: ......
Страница 8: ......
Страница 9: ...Chapter 1 General Service Safety Precautions...
Страница 16: ......
Страница 17: ...Chapter 2 Model and Application...
Страница 22: ......
Страница 23: ...Chapter 3 Compressor Motor and Component...
Страница 36: ......
Страница 37: ...Chapter 4 Servicing...
Страница 38: ...30 SERVICE HANDBOOK...
Страница 79: ...71...
Страница 80: ......
Страница 81: ...Chapter 5 Installation and Replacement...
Страница 96: ......
Страница 97: ...Liquid refrigerant migration to compressor FIGURE 6 1 Chapter 6 Operation...
Страница 108: ......
Страница 109: ...Appendix...
Страница 113: ...105 Reciprocating Compressor FIGURE A 2 Internal view of typical air conditioning compressor...
Страница 118: ...110 SERVICE HANDBOOK Notes...
Страница 119: ......