6.3 Input
The following illustration shows the menus for the input parameters.
Menu options on the lowest level are outlined in bold. The menu items
Zero point
and
Conversion factor
will
not
be shown if the unit mA is
selected (section 6.2).
6.3.1 Line monitor
• If you select
ON
for
LB
, an input current < 0.2 mA will be registered
as a lead break/open circuit (see section 5).
• If you select
ON
for
LK
, an input current > 22 mA will be registered as
a short circuit (see section 5).
If you wish to process the 0.2 mA input values as measured values,
you must deselect the lead breakage detection (Off LB). If not, an error
will be signalled within the measuring range.