Challenger10 Installation and Quick Programming Manual
To establish an event-driven IP connection:
1. On an LCD RAS, access the Install menu. See “Accessing the Challenger
menu” on page 20.
2. Press 9 [ENTER] to access the Communications menu, and then select
option 1–Setup H/W, to access the Setup menu.
3. Select option 1–Onboard, and then press [ENTER] to step through the
options. Change the default settings, if required (in particular, change
Ethernet to Yes).
Use the values advised by the site’s network administrator for the IP address,
subnet mask, and gateway address.
4. When returned to the Setup menu, press [0] [ENTER] to exit to the
Communications menu.
5. At the Communications menu, select option 2–Setup Paths, and then press
[3] [ENTER] to select path 3–MANAGEMENT SOFT.
6. Press [ENTER] to display the first item for path 3, and then select option
1–Main.
7. Press [ENTER] to step through the options, and change the default settings if
required (in particular, change Enabled to Yes).
You might also need to change the account code and the computer password
(default is 0000000000).
8. When returned to the Path menu select option 6–Path IP Address.
9. Press [ENTER] to step through the options, and program the following
settings (in particular, program the Titan computer’s IP address).
Use the default values (if applicable) for the Send and Listen IP Port numbers
(default is 3001) and UDP/IP.
10. Press 0 [ENTER] as needed to exit from the Communications menu.
11. In Titan, select Ports from the Admin menu.
12. In the port record select UDP/IP, enter a port number, description, Challenger
panel’s IP address, and IP Port number (for example 3001). Save the record.
13. Connect the Challenger panel’s Ethernet port at J19 (Figure 5 on page 11,
item 16) to the LAN or directly to the Titan computer via a Cat 5 cable.
14. Select Challenger from the Admin menu.
15. In the Challenger record, ensure the Challenger No. and Security Password
are the same as programmed via RAS, type the port number in the Port field,
and select UDP/IP as the communications mode. Save the record.
16. Select Open/System from the File menu, select Active System, and then save
the record. The connection indicator at the bottom of the Titan window
displays green to indicate a successful connection.