7. ALARM MANAGEMENT
7.1
Storage of data/errors
The appliance electronic controller is equipped with a system of acoustic and visual signals
to indicate the intervention of safety devices. The table below gives a list of the alarms
shown on the panel display
7.2
The software controls the following alarms:
Evaporator probe alarm (ALL 01)
Cause:
Exit from operating range (-50°C / +100°C) for over 30 seconds.
Probe is defective (REPLACE PROBE).
Beeper:
Activated (3 seconds, then a pause of 30 seconds) until the mute button is
pressed.
Display:
Alternates message “ALL 01” with standard display
Reset:
Automatically resets only when probe reading has returned to normal.
Core probe alarm (ALL 02)
Cause:
Exit from operating range (-50°C / +100°C) for more than 30 seconds during cur-
rent chilling cycle by temperature.
Effect:
Interruption of current chilling cycle by temperature and automatic start-up of
timed chilling cycle. Chilling by temperature push-button disabled.
Probe is defective (REPLACE PROBE).
Beeper:
Activated (3 seconds, then a pause of 30 seconds) until the mute button is
pressed.
Display:
Alternates message “ALL 02” with standard display
Alarm relay:
Not activated.
Reset:
Press the mute push-button (with beeper off).
Resets automatically if probe value returns to normal, but cycle remains in timed
mode. Alternatively, switch off the panel then turn it back on (stand-by).
Cell probe alarm (ALL 03)
Cause:
Exit from operating range (-50°C / +100°C) for over 30 seconds.
Probe is defective (REPLACE PROBE).