background image

animals deriving from the instrument violation, not proper or
wrong use or in any case not in accordance with the instrument
features.

3.4 - ELECTRICAL CONNECTION DRAWING

4 - OPERATING MODE

4.1 – FUNCTIONING OF THE COUNTING COMMANDS  

The counting can be enabled and disabled through the frontal key T,
or through the remote inputs CNT EN and RES.   
The operating mode of the key T is defined by the parameter

 "t",

the operating mode of the input CNT EN is defined by the parameter

"E"

 while the input RES always works as reset, i.e. it stops and

resets the counting when it is activated and moreover it has priority
on the other commands (when it is activated it doesn't allow the
starting of the counting).  
When the instrument is predisposed for the continuation of the
counting also without power supply, during the counting under
conditions of lack of supply the only active command is the RESET
one, which can be given only from the frontal key T.  
When the instrument is supplied through the battery it is not
therefore possible to make the counting start again once stopped.  
  

4.2 – FUNCTIONING OF THE DISPLAY   

The led SET/CNT is used to indicate the access into the
programming (flashing fast), the counting in action (flashing each
second), the counting interrupted before the term (lighted fixed) or
the counting finished and the state of reset (off).   
After the reset,  the display visualizes 0000 if the counting mode is
programmed as UP (par. 

"C"

 = 1) or it visualizes the programmed

set value if the counting mode is programmed as DOWN (par.

 "C"

 =

2).  
During the counting, the display visualizes the value of time that
spends in UP or in DOWN mode.  
If the back-up mode has been programmed to continue the counting
in action without power supply, the display remains lighted but with
an inferior brightness (with the purpose to limit as much as possible
the absorption from the battery).

4.3 - OUT1 OPERATING MODE

The instrument can be programmed by the parameter 

"F1"

 to

operate in any of the following 5 modes:
F1 = 1 -  DELAYED : 
On receiving the START signal, the instrument starts counting time.
When the set time value “t1” has been reached, the instrument
enables the output OUT1. 
The output is disabled by the RESET signal.

F1 = 2 - FEEDTHROUGH : 
On receiving the START signal, the instrument enables the output
OUT1. 
The output is disabled when the set time value “t1” has been
reached. 
The output will be enabled again after the transmission of a RESET
signal and a subsequent START signal.

F1 = 3 - ASYMMETRICAL OSCILLATOR START ON: 
This operating mode allows the user to enter two SET times “t1” and
“t2”, and therefore also involves the "S2" parameter . 
On receiving the START signal, the output OUT1 is immediately
enabled and remains enabled for the time period t1. 
Then the output is disabled and remains disabled for the time period
t2. 
This procedure goes on until a RESET signal is transmitted.

F1 = 4 - ASYMMETRICAL OSCILLATOR START OFF: 
This operating mode allows the user to enter two SET times “t1” and
“t2”, and therefore also involves the "S2" parameter . 
On receiving the START signal, the output remains disabled until
the set time period “t1” has expired. 
Then the output is enabled. 
The output is disabled again when the set time period “t2” has
expired. This procedure goes on until a RESET signal is transmitted.

F1 = 5 - ONE CYCLE ASYMMETRICAL OSCILLATOR START OFF:
The operation results similar to the "F1"=4 with the only difference
that only one cycle of OFF/ON is performed.   
To the start signal the output OUT1 remains disabled for the time
“t1".
When the time “t1” is expire the output will be on for the time “t2”.
The cycle will be enabled again after the transmission of a RESET
signal and a subsequent START signal.

TECNOLOGIC spa - TT 73

 

- OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 3

Содержание TT 73

Страница 1: ...G MODE 4 4 OUT 1 OPERATING MODE 4 3 DISPLAY OPERATING MODE 4 2 COMMANDS OPERATING MODE 4 1 OPERATING MODE 4 ELECTRICAL CONNECTION DRAWING 3 4 ELECTRICAL CONNECTIONS 3 3 MECHANICAL MOUNTING 3 2 USE ALLOWED 3 1 INSTALLATION AND USE ADVICES 3 PARAMETERS LOCK 2 3 PARAMETERS PROGRAMMING 2 2 SET POINT PROGRAMMING 2 1 PROGRAMMING 2 FRONT PANEL DESCRIPTION 1 2 GENERAL DESCRIPTION 1 1 INSTRUMENT DESCRIPTIO...

Страница 2: ...dify the Set Point To have again access at the parameters repeat the same procedure pushing key P and selecting uL finally go out from the parameters lock modality 3 INSTALLATION AND USE ADVICES 3 1 USE ALLOWED The instrument has been projected as measure and control device built according to EN61010 1 for the altitudes operation until 2000 ms The use of the instrument for applications not express...

Страница 3: ...rior brightness with the purpose to limit as much as possible the absorption from the battery 4 3 OUT1 OPERATING MODE The instrument can be programmed by the parameter F1 to operate in any of the following 5 modes F1 1 DELAYED On receiving the START signal the instrument starts counting time When the set time value t1 has been reached the instrument enables the output OUT1 The output is disabled b...

Страница 4: ...ction of delay with the time t3 while if F1 2 or 3 the output OUT 2 operate with the feedthrough function always with the time t3 In the programming mode of the time t3 the display shows t3 i to indicate that the time t3 is independent F2 4 Same function of OUT1 time t1 with time t3 relative to t1 in advance The choice of this mode of operation enable the set t3 that it has the same range time S1 ...

Страница 5: ...ing of the CNT EN input the counting is stopped This operating mode is recommended when the user wants to control the timer using voltage signals In fact with an appropriate interface eg an external relay the timer is reset and starts counting when voltage is supplied and stops when voltage is cut off just like a conventional timer In this functioning mode the T frontal key works only as reset 5 P...

Страница 6: ...under warranty against construction vices or defected material noticed within 12 months from delivery date The warranty is limited to the repairs or to the substitution of the instrument The eventual opening of the housing the violation of the instrument or the wrong use and installation of the product means the automatic decay of the warranty In case of defected instrument noticed in warranty per...

Страница 7: ...uracy 0 1 fs Counting autonomy in case of power failure 10 hrs approx with full charge battery Inputs delay 15 m sec Max Display 4 Digit Red h 14 mm Compliance ECC directive EMC 89 336 EN 61326 ECC directive LV 73 23 and 93 68 EN 61010 1 7 5 INSTRUMENT CODE TT 73 a b c d e ff a POWER SUPPLY F 12 VAC VDC Y 24 VDC A 24 VAC C 110 VAC D 230 VAC b INPUTS C Free voltage contacts V Voltage signals the sa...

Отзывы: