background image

IST-2136.IC01.01

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.6/10

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) ITALY 

Tel. +39 02 26922890 - Fax +39 02 2133734

 

 

 

Important

:

  Once  installation  is  completed,  power  up  the  unit,  it  is  not  necessary  to  make  any  adjustment.  Wait 

about 20 to 30 minutes and then, only if it is requested, carry out the 

”Operation Check” 

(

see “

Test”

). 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time, the sensor's life is more 

than 5 years from the date of installation. After this period the yellow LED “

FAULT

” flashes every 3 seconds, this is 

only a warning, the detector continues to operate normally, but then is necessary replace and / or send the detector 
back to the supplier to replace the “

Sensor

” with a new one.  

Periodical testing

: depending on the use, we advise to carry out working tests every 6÷12 months. As explained in 

chapter “

Tests

”. 

For five years it is not necessary to calibrate the sensor.

 

Note:

  the  detector  is  not  able  to  detect  gas  leaks  occurring  outside  the  room  where  it  is  installed,  neither  inside 

walls or under the floor. 

Warning:

 Consider that in polluted environments or with temperature, pressure or Humidity more than the declared 

limits, the useful life of the sensor can be reduced. 

TESTS 

PAY  ATTENTION

This  procedure  has  to  be  made  with  extreme  attention  and  by  authorized  and  trained 

people; because will activate the alarm devices connected to the outputs (relays and mA signal). 

Operation Check and Calibration check with Gas

:

 are different code protected functions. To access these func-

tions is necessary to insert the relevant “

Code

" through the keys F1 and F2. To have the key pressure recognized, 

hold pressing it for around a second (

until the Green LED doesn't switch off for a moment

). Then the next key can be pressed. 

In case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Test Kit, Sample Gas Cylinders

 (

only for Calibration Check

) please, only using a mixture: 

Sample Gas Cylinder for SPAN Calibration 

Tecnocontrol Code 

1% Volume 

Carbon dioxide (CO

2

)

 

in nitrogen

 

Available on request 

Sample Gas Cylinder for ZERO Calibration

 

 

Pure Zero Air (less than 5 ppm CO

2

Available on request 

You can use 

disposable cylinder, complete with adjust valve

. It is also necessary to use 

the Test kit 

Tecno-

control model TC011 or TC014

.

 

 “INSTRUMENT  OPERATION  CHECK”  (

Check  Code

:  F2,  F2,  F1,  F1)

this  function  allows  to  effect  a  functional 

test of the equipment. After having inserted the "

Check C

ode

", all Led are switched off and all the relays are deac-

tivated. Then they will switch on in sequence, the Led, from the yellow up to the 3

rd

 red. To the lighting of the vari-

ous Led it corresponds the activation of the relevant relays (

relay "FAULT" with the yellow Led, relay "ALARM1" with the 1

st

 red 

Led,  relay  "ALARM2"  with  the  2

nd

  red  Led,  relay  "ALARM3"  with  the  3

rd

  red  Led

).  At  the  end  all  the  Led  will  remain  lighted  for 

around  5  seconds,  then  the  detector  returns  at  the  conditions  of  normal  operation.  It  is  advisable  to  perform  this 
operation every 12 months according to the use. 

Note

: this function is not working if the 1

st

 and/or the 2

nd

 and/or the 3

rd

 red Led have already turned on. 

“CALIBRATION  CHECK  WITH  GAS”  (

no  Code  required

)

:

 

using  the  gas  mixture  indicated  above,  this  function  is 

used to control the correct response to the gas and can be made after the installation. But it should be done during 
the periodic maintenances, to verify the effective functioning of the detector. 

NOTE:

 please use, the gas mixture as indicated above. Normally it is sufficient to perform the 

Calibration check with 

gas

, (

1%Volume CO

2

 Cylinder in nitrogen

) but you can also carry out 

Checking Zero

 (

Pure Zero Air Cylinder

). 

Insert  the  TC011/TC014  over  the  sensor  holder,  adjust  the  sample  gas  bottle  valve  as  the  flow  meter  indicates 
around 0.3 l/mins (

see Fig.3

), wait for 3 minutes and check that the instrument activates Alarms as shown in chapter 

Operational  Description

”. 

If  the  result  is  very  different,  contact  our  customer  service. 

Then  close  the  gas  bottle,  re-

move TC011/TC014. The detector will slowly returns at the conditions of normal operation. 

NOTE

: further to the above, If the mA output is also used, 

insert the TC011/TC014 over the sensor holder,

 adjust 

the  sample  gas  bottle  valve  as  the  flow  meter  indicates  around  0.3  l/mins  (

see  Fig.3

),  verify  with  a  voltmeter  con-

nected to the Test-Point “

TEST mV

” (

TP1 and TP2

),

 

(

see fig.2

) the value reach the 

mV

 value as shown in 

Table 4 on col-

umn  6

  [corresponding  to  mA  output  value  (

±0.56  mA

)  as  indicated  in 

column  7

.  T

he  central  unit  should  be  display 

about the value indicated in 

column 8

]. If the result is very different, contact our customer service. Then, close the 

gas bottle; move away the 

TC011/TC014

. Then, the mA output will slowly decrease up to 4mA. 

Example

 if you have to verify a SE136 IC2 using a cylinder with Pure Zero Air, the mA output will be 4.0 mA (cor-

responding about to 40 mV measured on "

TESTmV

”). Then using a cylinder with 1%volume (= 10000 ppm) CO

2

 in 

nitrogen, the mA output will be approximately 12.0 mA (

±0.56mA

) (corresponding value from 114 to 126mV  meas-

ured on "

 TESTmV

”). 

 

 

FR

 

 DESCRIPTION 

Les 

SE136 IC2

 sont des sondes de détection de CO

2

, avec capteur “

Infrarouge” (

NDIR – Nondispersive Infrared Sen-

sor

)

, utilisées dans les systèmes centralisés de détection de gaz destinés pour la première aux alarmes pour labo-

ratoires,  industries  alimentaires,  caves  vitivinicoles  et  brasseries  et  pour  la  seconde  aux  contrôles  de  la  quantité 
d’anhydride carbonique présente dans les serres. La sonde est constituée d’un boîtier contenant le circuit électro-
nique ainsi que les borniers de raccordement. Le capteur est à l'intérieur du porte capteur, dans la partie inférieure 
du boîtier. 

Содержание SE136IC2

Страница 1: ...empo di risposta Response Time Temps de réponse 60s T90 105s dipendente dal valore misurato depend ing on the measured value dépend de la valeur mesurée Ripetibilità di zero Zero Repeatability Zéro répétitivité 1 FS Fondo Scala Full Scale fond d échelle Precisione Accuracy Précision 0 02 vol 200ppm 5 del valore misurato of measuring value de la valeur mesurée Tempo di Preriscaldo Warm up time Temp...

Страница 2: ...e e arriva al rivelatore Il rivelatore è doppio il primo definito attivo ha un filtro ottico per il gas da misurare mentre il secondo chiamato riferimento ha un filtro con una lunghezza d onda diffe rente Il rilevatore attivo viene usato per rilevare il gas mentre il rivelatore di riferimento fornisce il valore di zero La differenza di segnale tra i due rivelatori fornisce il valore di concentrazi...

Страница 3: ...ssima con alimentazione 12Vcc 10 è 50ohm mentre a 24Vcc 10 è 500ohm vedi Fig 4 Il morsetto d alimentazione sulla scheda principale è ad innesto e va sfilato per collegare i cavi Prestare atten zione nel reinserirlo dato che è polarizzato Invece quelli dei Relè d allarme posti sulla scheda uscite sono fissi I relè di tipo sigillato hanno un contatto libero da tensione SPST 1 Singolo Contatto Single...

Страница 4: ...la con CO2 a 1 vol 10 000ppm in Azoto l uscita in mA dovrà essere circa 12 mA 0 56mA cioè 114 126mV su TESTmV EN DESCRIPTION The SE136 IC2 series are gas detectors able to detect CO2 Carbon Dioxide by employing a NDIR Non dis persive Infrared Sensor and find their best application in centralized alarm systems for laboratories food indus tries Wineries Breweries or environments Greenhouses where mo...

Страница 5: ...e to workers OSHA Occupational Safety and Health Administration of the U S Department of Labour and COSHH Control Of Substances Hazardous to Health in Europe FAULTS the Yellow LED FAULT illuminates the S output falls down to 0mA The different faults are listed below and the FAULT normally activated relay NC contact will deactivate The FAULT relay if necessary can be used both to signal remotely an...

Страница 6: ...ith the yellow Led relay ALARM1 with the 1st red Led relay ALARM2 with the 2nd red Led relay ALARM3 with the 3rd red Led At the end all the Led will remain lighted for around 5 seconds then the detector returns at the conditions of normal operation It is advisable to perform this operation every 12 months according to the use Note this function is not working if the 1 st and or the 2 nd and or the...

Страница 7: ...utre dite de référence comporte un filtre de longueur d onde différente et servant de référence La différence entre ces deux signaux permet de mesurer la concentration de gaz L unique cause d interférence peut être donnée par la présence de vapeur d eau qui absorbe l infrarouge Préchauffage à partir du moment où la sonde est alimentée commence le préchauffage du capteur signalé par le clignotement...

Страница 8: ...contre ceux des relais d alarmes montés sur la carte de sortie sont fixes Les relais de type solide state possèdent un contact libre de tension SPST 1 Unique Contact Single Pole Single Throw qui peut être paramétré NA NO Normalement Ouvert ou NC NF Normalement Fermé selon position du Dip Switch n 4 Tableau 3 Les Dip Switch de 1 à 3 servent à déterminer les seuils d alarmes en fonction des concen t...

Страница 9: ...V TP1 et TP2 voir Fig 2 on obtient la valeur en mV indiquée au Tableau 4 Colonne 6 ou bien que la sortie en mA augmente jusqu à la valeur indiquée dans la Colonne 7 0 56mA et que la centrale à laquelle est raccordée la sonde indique la valeur contenue en Colonne 8 Si le résultat est très différent contactez notre ser vice Une fois la Vérification terminée fermer la bouteille et enlever le kit TC01...

Страница 10: ...a Gas heavier than air gaz plus lourd que l air Fig 1 Dimensioni Size Dimensions Fig 2 Schema di collegamento Wiring diagram Schéma S 12 24V mA 1 2 3 4 ON OFF SET ALARM 1 ALARM 2 ALARM 3 FAULT Scheda Uscite Relé Relays Output Board Sortie sur Realis TESTmA 12 24Vdc Alimentazione Power Supply Alimentation Centrale rivelazione gas Gas Central Unit Centrale de détection RL Uscita in 4 20 mA 4 20 mA O...

Отзывы: