tecn@
WELDERS ITEM 8201N ÷ 8214N
EDITION: MAY 2008 PAGE 4 OF 32
2 TECHNICAL FEATURES
2.1 IDENTIFICATION DATA
Item
Year of manufacturing
Serial number
Supply voltage
V
Frequency
Hz
Optional:
8230 Valve to stop the flow of the water cooling when the machine is off and flow switch
which makes the welder stop if the cooling water does not circulate.
8232 Rotary selector for the welding program recalling.
8234 Double stroke control device with pneumatic foot instead of key one.
8235 Cylinder 1242 daN (
∅
125 double stage) total stroke 100 mm.
8236 Adjustable double stroke for cylinder 736 daN (standard).
8237 Adjustable double stroke for cylinder 1242 daN (option 8235).
8238 Low pressure squeeze for cylinder 736 daN (standard).
8239 Low pressure squeeze for cylinder 1242 daN (option 8235).
8240 Proportional valve.
8241 Constant energy operating mode.
2.2 ELECTRICAL DATA
Item
8201N 8202N 8203N 8204N 8206N 8207N 8208N 8209N 8211N 8212N 8213N 8214N
Nominal power at 50 %
duty cycle
kVA
63
80
100
125
63
80
100
125
80
100
125
160
Maximum welding power
kVA
230
295
420
460
170
230
315
350
135
205
225
650
Short circuit secondary
current
kA
40
44
52
54
29
34
39
41
20
25
26
65
Maximum welding current
on aluminium
kA
36
40
47
49
26
30
35
37
18
22
23
59
Maximum welding current
on steel
kA
32
35
41
43
20
27
31
32
16
20
20
52
Secondary thermal current
at 100 %
A
6200
6800
7000
8400
6200
6800
7000
8400
6800
7000
8400
9300
Secondary no load
alternate voltage
V
7.1
6.3
5.6
5.0
8.3
7.5
6.7
6.1
10
9
8
7.1
10.5
9
8
7.3
7.1
6.3
5.6
5.0
8.3
7.5
6.7
6.1
10
9
8
7.1
10.5
9
8
7.3
8.3
7.5
6.7
6.1
10
9
8
7.1
10.5
9
8
7.3
12.1
Delayed fuses
(380
÷
415V)
(220
÷
240V)
A
A
125
200
160
250
200
315
250
400
125
200
160
250
200
315
250
400
160
250
200
315
250
400
315
-
Mains cables section *
380
÷
415V - L=10m
380
÷
415V - L=30m
380
÷
415V - L=60m
220
÷
240V - L=10m
220
÷
240V - L=30m
mm
2
mm
2
mm
2
mm
2
mm
2
50
50
95
2x35
2
×
70
70
70
2
×
70
2x70
2
×
95
95
95
2
×
50
2x95
2
×
120
2
×
50
2
×
50
2
×
95
2x120
2
×
150
50
50
70
2x35
2
×
50
70
70
95
2x70
2
×
70
95
95
2
×
35
2x95
2
×
95
2
×
50
2
×
50
2
×
70
2x120
2
×
120
70
70
70
2x70
2x70
95
95
95
2x95
2x95
2
×
50
2
×
50
2
×
50
2x120
2x120
2
×
70
2
×
70
2
×
120
-
-
Supply transformer
minimum power **
kVA
266
341
480
532
197
266
364
405
156
237
260
727
* Section for every phase, calculated for PVC insulated, single conductor cables, considering the welder working at
the maximum welding power and a 4% voltage drop on cables.
** Approximate value, calculated for a three phase transformer with a 4% short circuit voltage, with 6% voltage drop
on transformer and a 4% voltage drop on cables, with the welder adjusted for the maximum welding power.