TEC247 Fire & Extinguishant Control Panel
– INSTALLATION & OPERATION MANUAL
DOC NO. PRMAN-0003 TEC247 Rev 04.12 191209.docx
- 15 -
E. &O.E.
9.
TECHNICAL SPECIFICATIONS
Operating Input Voltage
100 V AC to 250 V AC
Quiescent Current @ 24 V DC
95 mA
Sounder & Initiate Output
3x 24 V DC 500 mA (across all)
Detector Output
22 V DC
Discharge Output
24 V DC 1 A
Potentially Free Relays
30 V DC 1 A (non-inductive)
Weight (excl batteries)
4.5 kg
Dimensions of Lid (H x W) mm
322 x 345
Dimensions of Base (H x W) mm
316 x 338
Depth mm
80
10.
WARRANTY
General Terms and Conditions are available from the Technoswitch website
. Alternatively,
please contact your local Sales Office for further information.
11.
DISCLAIMER
Although the contents of our product literature have been prepared with the greatest care, Technoswitch can
accept no liability whatsoever for any direct or indirect damages of any kind that may arise due to either errors or
omissions in them, or amendments to products or other specifications following publication.
12.
REVISION INFORMATION
Revision
Date Issued
Reason for Change
Reference
Rev 02.00
2016/02/17
PSU2AEN PSU Added
ENGCH-0031
Rev 03.00
2016/04/26
Firmware Version 02.00
ENGCH-0040
Rev 03.01
2016/08/16
Product Firmware Update for Enhanced Functionality
ENGCH-0046
Rev 03.02
2016/11/03
Product Codes Updated
DCR-053
Rev 04.00
2017/03/29
Firmware, Hardware and Product Code Change
ENGCH-0045
Rev 04.10
2017/07/19
Update and Add Technical Information on Outputs
DCR-086
Rev 04.11
2019/01/24
Updated Technoswitch Logo
DCR-154
Rev 04.12
2019/12/09
Updated Cape Town office address
DCR-187