Techno GR F3S-TGR-SB2 Series Скачать руководство пользователя страница 10

SB series 

User’s manual 

 19

8 OPERATING 

PROCEDURES 

8.1 

SETTING THE INTERNAL DIP-SWITCHES 

x

Disconnect the barrier’s power supply and remove the side on the 
connector side of the receiver, so that you can reach the two banks 
four-way dip-switches located there.

x

Use a suitably sized screwdriver to set the dip-switches as per the 
required configuration according to the following tables.

8.1.1 

SELECTION OF RESET MODE  

Single switch number 4 

Reset  

OFF Manual 
ON Automatic 

8.1.2 RELAY 

MODULE 

MANAGEMENT 

Single switch number 3 

Function 

OFF Disenabled 

 

ON Enabled 

VERY IMPORTANT WARNING!!!

In every unit are present two different dip-switch banks and that two 
banks must be set in the same way.
The two dip-switches on the receiver side must have the same 
configuration.
The configuration of the two, number 3 dip-switches (relay module 
management) on the transmitter side must be the same as the 
configuration of the two, number 3 dip-switches on the receiver  side, 
therefore, if you alter these dip-switches on the receiver you must also 
alter those on the transmitter by removing the side panel on the 
connector side. 
If the number “3” dip-switches are not identical, the RX-TX system will 
not work.

SB series 

User’s manual 

 20

9  MUTING, OVERRIDE AND FLOATING BLANKING 

FUNCTIONS 

9.1 

GENERAL INFORMATION ON THE THREE FUNCTIONS  

The 

muting, override 

and

floating blanking 

functions enable the 

barrier (or a part of it) to be bypassed when it is working for 
operational requirements. As required by current standards, the 
barrier is provided with inputs for the activation of these functions. It 
should however be remembered that these functions basically 
override the system and they should therefore be used with due 
care. 

9.2 MUTING 

FUNCTION 

As mentioned in the introduction, the 

muting

 function can be enabled with any 

barrier by simply connecting the LMS muting indicator when the barrier is 
switched off, as described in section 6. 
The presence of this indicator is recognised when the barrier is switched on. If 
its presence is detected, the barrier will enable the 

muting

 function and if its 

presence is not detected the barrier will ignore any request for 

muting

.

It is 

important to note that if the 

muting

 indicator is connected when the 

barrier is already connected to the power supply, it will not be 
recognised and the 

muting

 function will not be enabled.

 Once enabled, if 

the indicator develops a fault or is removed without first disconnecting the 
barrier’s power supply, it will signal an error with the 

muting 

light, as described 

in section 10.  
To disenable the 

muting

 function, therefore, the barrier’s power supply must 

be turned on without the LMS muting indicator connected.
In brief: this function, present on all barriers, is enabled and disenabled by 
means of the following simple procedure: 

-

Disconnect the barrier’s power supply. 

-

Connect the appropriate LMS and the muting sensors (see sec. 6 )  

-

Restore the barrier’s power supply. 

Bypass the muting function as follows. 

-

Disconnect the barrier’s power supply. 

-

Disconnect the LMS device and the muting sensors ( see sec. 6 ) 

-

Restore the barrier’s power supply. 

Содержание F3S-TGR-SB2 Series

Страница 1: ...to the following directives 98 37 EC Machinery Directive 73 23 EEC Low Voltage directive resp 93 68 EEC EN 61496 1 1997 prEN 61496 2 1997 DIN V VDE 0801 1990 and amendment A1 1994 EN 50081 2 1993 EN...

Страница 2: ...UNCTIONS 20 9 1 GENERAL INFORMATION ON THE THREE FUNCTIONS 20 9 2 MUTING FUNCTION 20 9 3 DESCRIPTION OF SINGLE MODULE MUTING AND MODULAR MUTING 21 9 3 1 DEFINITION OF MODULE 21 9 3 2 SINGLE MODULE MUT...

Страница 3: ...ces provide coverage of the protected area and generate a beam of infrared rays which are able to detect an object located inside their field of operation They comply with the requisites for level 2 S...

Страница 4: ...ved 2 Manual reset normal operating mode is only restored after the object has been removed and the reset button has been pressed To enable the muting function the LMS muting indicator must be connect...

Страница 5: ...response time in seconds T2 barrier s response time in seconds K 1600 mm s approach speed of the body to the danger zone C 1200 0 4 H H height of the optical rays compared to the floor S safety distan...

Страница 6: ...cal assembly The securing brackets for the bars slide in the container s grooves so that their ends can be placed at an equal distance from each other OK NO NO SB series User s manual 12 6 CONNECTIONS...

Страница 7: ...SB series User s manual 13 6 2 CONNECTIONS WITH TGR SB RELAY MODULE SB series User s manual 14 Following the connection scheme if TGR SB is connected in presence of muting activator MSB L or MSB T...

Страница 8: ...c device such as a PLC SB series User s manual 16 6 4 CODES AND SPECIFICATIONS OF AVAILABLE MODELS The columns with Number of modules and Number of optical units per module refer to operating manageme...

Страница 9: ...65 210 42 10 21 SBx HR 1650 1650 1712 231 45 11 21 SB series User s manual 18 7 ALIGNMENT PROCEDURE After completing correct mechanical assembly and connections as described in the previous sections t...

Страница 10: ...tional requirements As required by current standards the barrier is provided with inputs for the activation of these functions It should however be remembered that these functions basically override t...

Страница 11: ...more modules transparent until even the whole barrier has been bypassed Should a muting request be made for modules that are not managed when in single module muting mode for example bypassing of the...

Страница 12: ...tection barrier S is connected to the control panel and A1 A2 B1 and B2 are temporarily excluded for the passage of the box via sensors that enable muting The contacts for these sensors are controlled...

Страница 13: ...the receivers of the sensors are mounted on the transmitter side of the barrier in order to avoid interference x The system is protected against the possibility of faults due to damage to the wires ho...

Страница 14: ...umber of 20 The following examples can help to understand Example 1 total optic rays 102 optic useful for blanking 31 The zone can be higher than 20ray but the unit can only mask 20 rays SB series Use...

Страница 15: ...rrier If it flashes there is a short circuit on the outputs x POWER Green when lit this indicates that the receiver is powered The leds placed on the transmitter indicate the following x POWER Green w...

Страница 16: ...r and the dangerous parts of the machinery x Check that there is no external damage to the barrier and or to the external electrical connections The interval between the above actions depends on the i...

Страница 17: ...Resolution 35 mm for SBx models 14 mm for SBx HR Variable for SBx K models according to amount of rays and height protected x Operating temperature 10 to 55 C x Humidity 15 to 95 non condensing x Safe...

Страница 18: ...al 35 SB series User s manual 36 16 NOTE Distributed by OMRON Europe B V Wegalaan 67 69 2132JD Hoofdorp The Netherlands Sensor Business Unit Carl Benz Str 4 D 71154 Nufringen Germany Tel 49 7032 811 0...

Отзывы: