Index specification
To process sensor values in the controller, specification and selection of the sensor address
(1-8)
and
the index (1-6) is necessary.
Indices can be selected for the following values:
Index Value
1
Room temperature
with offset values
of the +/- adjustment and the slider switch
(for evaluation “
RAS
” in the controllers UVR16x2, RSM610, CAN-I/O45, UVR1611
and UVR63-H from version 7.2)
2
Measured room temperature (
no offset values
of the +/- adjustment and the slider
switch (e.g. for the controller UVR61-3)
3
Relative room humidity (only type RAS-PLUS /F)
4
Dew point temperature (only type-RAS PLUS /F)
5
Fixed value 20°C
with offset values of the +/- adjustment and the slider switch
(Use as a
remote control
for the controllers UVR16x2, UVR1611 and UVR63-H)
6
Room temperature
with offset values
of the +/- adjustment and the slider switch
(+51,2K for normal operation, +102,4K for lowering mode, +153,6K in standby
mode) for evaluation of the position of the slider switch. The output is a dimension-
less value without a decimal point.
UVR16x2, RSM610, CAN-I/O45:
The measured values are parameterised in the menu
"
DL bus
“.
UVR1611
:
The measurements are parameterised as
analog
network inputs:
NW.Node:
Sensor
address
Anal.NW.Outp.: Index of the measured value
Source: DL
TAPPS2 Programming UVR1611:
A still unused network input variable must be selected for each new value. The values of in-
dices 1 and 5 displayed at the network input do not correspond to the temperatures and are
only correctly displayed in the controller in the measured values overview and in the func-
tions.
Analog
network input
Source: DL
Sensor address
Index of the
measured value
1
3
4
2
5