11
Address in the DL-bus network DL ADR
Upon querying by the controller
ESR31, UVR63
(from version 1.0),
ESR21, UVR61-3
and
UVR63-H
(from version 5.0),
UVR1611
(from version A3.00), plus
UVR16x2, RSM610
and
CAN-I/O45
the sensor returns the corresponding measured value. The request is made up of
the address of the sensor and index of a measured value recorded there.
Each member of the DL-bus network must
have its own address so that it can send
values to a controller.
Factory setting: DL 1
After a long key press "1" flashes
Selection of the desired address by a short
key press.
Adjustment range
: DL 1 to DL 8
Confirmation of the desired address by a
long key press.
Amongst those controllers that have no bidirectional data link (e.g. HZR65), i.e. amongst
those for which the
RAS-PLUS
can only be used as a
remote display
, this menu option is
still displayed but has no effective function and must therefore not be observed.