10
Time before jumping back to the 1st display TIME R
Entry 0 = There is no jumping back to the display
of the 1st value.
Factory setting: 0
After a long key press "0" flashes
Selection of the desired time via a short key press.
Confirmation of the desired time via a long key
press.
Entry 60 = After 60 seconds without pushing of
the button jumping back from one of the addition-
al programmed values to the first display value
(room temperature) occurs.
Adjustment range
: 0
–
200 sec in 1 second steps
The jump back occurs only from the additionally programmed display values, not from one of
the base values.
Note: If the continuing display TIME N is activated (≠0), then TIME
R has no effect.
Address in the DL-bus network DL ADR
Upon querying by the controller
ESR31, UVR63
(from version 1.0),
ESR21, UVR61-3
and
UVR63-H
(from version 5.0),
UVR1611
(from version A3.00), plus
UVR16x2, RSM610
and
CAN-I/O45
the sensor returns the corresponding measured value. The request consists of
the address of the sensor and the index number of a measured value.
Each member of the DL-bus network must have
its own address so that it can send values to a
controller.
Factory setting: DL 1
After a long key press "1" flashes
Selection of the desired address via a short key
press.
Adjustment range
: DL 1 to DL 8
Confirmation of the desired address via a long
key press.
Among those controllers that have no bidirectional data link (e.g. HZR65), i.e. those for which
the
RAS+DL
can only be used as a
remote display
, this menu option is still displayed but has
no effective function and must therefore not be observed.