Error code display 

When Air conditioner has problem, the display will show different error code related to 

different problems.   

Reason Display 

Solution 

TA abnormal(broken 

circuit or short circuit) 

E1

 

See the detail solution 

TE abnormal(broken 

circuit or short circuit) 

E3

 

See the detail solution 

TW abnormal(broken 

circuit or short circuit) 

No error code 

No error report, stay the 

same 

Water full 

P1

 

See the water full alarm 

function 

 

二、

Error solution

 

1. TA abnormal, indoor shows E1 keep lighting, air conditioner can run without any 

stop except the heating mode, other protection still valid. If under auto mode to 

choose the mode according to the environment temperature, please choose fan mode 

to run. If under cooling mode, the machine continuous running, If under dehumidifier 

mode, fan motor and compressor do not working, the up motor is set with low fan speed. 

 

2. If under cooling or dehumidifier mode, TE abnormal, indoor will show “E3” keep lighting. 

The normal anti-frozen protection function no more working. Cooling, dehumidifier mode, carry 

out stopped for 5min after compressor continuous working more than 30min. If under heating 

mode, indoor shows”E3” keep lighting, air conditioner will stop running.   

 

3. TE and TA happen during the same time, TE error code’s special operation status will has 

priority 

 

 

Remark

 

TA: Indoor environment temperature 

TE: evaporator coil temperature 

TS

Set up temperature 

TW

condensor coil temperature

 

Содержание Softy Softy Plus

Страница 1: ...ctions carefully before operating the appliance or carrying out maintenance work Observe all the safety instructions failure to observe the instructions may lead to accidents and or damage Store these...

Страница 2: ...airconditionerwillrecovertonormalstatus Under dehumidifying mode air conditioner will control compressor work status automatically according to indoor air temperature under cooling heating or dehumidi...

Страница 3: ...PCBboard replacemainPCBboard checkconnectionstatusofcompressor motorandfanmotor pumpingout YES NO YES NO NO Replace PCB NO YES YES Draw out power supply plug and about five seconds later insert again...

Страница 4: ...Indoor fan motor does not run After draw out power supply plug and more five seconds insert plug again Replace PCB PCB failure Whether input voltage of fan motor is satisfied or not Whether the core o...

Страница 5: ...ore failure Replace button Liquid crystal failure Replace batteries Normal Whether the LCD of remote controller displays normally or not Whether battery voltage is less than 2 5 V or not remote contro...

Страница 6: ...ation make sure that conduct wire on circuit panel whether there is jumper loop or not diode location Conduct wire and member are damaged resulting from easy to bend and shock due to coarse treatment...

Страница 7: ...nect with power supply Check voltage 1 Whether is there normalAC voltage on XB or not 2 The DC voltage on IC5 input DC12V output DC5V Rectification circuit mistake Drop down transformer does not work...

Страница 8: ...hoose the mode according to the environment temperature please choose fan mode to run If under cooling mode the machine continuous running If under dehumidifier mode fan motor and compressor do not wo...

Страница 9: ...1111220000000211112032000045 Some models have no content inside dashed frame...

Страница 10: ...www technibel com...

Отзывы: