1-3-3 Detailed process

No

Malfunction 

Check point 

Reason 

1

Disconnection power supply and 

        check fuse on PCB

Damage or not

Voltage exceeding

Fan motor short

2

Connect with power supply  

Check voltage

1.Whether is there normal AC voltage on XB or not?

 
2.The DC voltage on IC5

   input DC12V   output DC5V

Rectification circuit mistake

 

Drop-down transformer does not 

    work

 

3

Special protection mode

Check voltage

Circuit malfunction

1.Check the control load for various relays

   Relay disconnect 0.5V

   Relay connect 6V

Relay malfunction

6

Содержание Softy Softy Plus

Страница 1: ...ctions carefully before operating the appliance or carrying out maintenance work Observe all the safety instructions failure to observe the instructions may lead to accidents and or damage Store these...

Страница 2: ...airconditionerwillrecovertonormalstatus Under dehumidifying mode air conditioner will control compressor work status automatically according to indoor air temperature under cooling heating or dehumidi...

Страница 3: ...PCBboard replacemainPCBboard checkconnectionstatusofcompressor motorandfanmotor pumpingout YES NO YES NO NO Replace PCB NO YES YES Draw out power supply plug and about five seconds later insert again...

Страница 4: ...Indoor fan motor does not run After draw out power supply plug and more five seconds insert plug again Replace PCB PCB failure Whether input voltage of fan motor is satisfied or not Whether the core o...

Страница 5: ...ore failure Replace button Liquid crystal failure Replace batteries Normal Whether the LCD of remote controller displays normally or not Whether battery voltage is less than 2 5 V or not remote contro...

Страница 6: ...ation make sure that conduct wire on circuit panel whether there is jumper loop or not diode location Conduct wire and member are damaged resulting from easy to bend and shock due to coarse treatment...

Страница 7: ...nect with power supply Check voltage 1 Whether is there normalAC voltage on XB or not 2 The DC voltage on IC5 input DC12V output DC5V Rectification circuit mistake Drop down transformer does not work...

Страница 8: ...hoose the mode according to the environment temperature please choose fan mode to run If under cooling mode the machine continuous running If under dehumidifier mode fan motor and compressor do not wo...

Страница 9: ...1111220000000211112032000045 Some models have no content inside dashed frame...

Страница 10: ...www technibel com...

Отзывы: