INSTALLATION RETURN WATER TEMPERATURE SENSOR

• Connect the temperature sensor (

SD1

on diagram 

1005753

) to the supplementary

heating electronic controller (

B1

) located in the heating control box (Terminal 

S1

).

• In order to ensure that this sensor works correctly:

- ensure that the sensor is correctly secured to the piping,
- use thermoconductive paste to improve conductivity (not included),
- insulate the assembly with insulating foam (not included).

• Two cases:

1)

Tank mounted on the unit.

- The sensor, equipped with its cable (supplied with the module) is to be installed in

the location provided on the unit's water inlet. See drawing.

2)

Tank mounted separately.

- The sensor is placed on the installation's water return line. Use a metal clamp.
- This connection may be extended with a 2-conductor cable, min. size 0.5 mm

2

and

max. length: 25 meters.

To avoid problems related to electromagnetic disturbances, this cable must not be routed near power
cables.

SUPPLEMENTARY HEATING ALARM REPORT

• A potential-free change-over contact (2 A resistive, 250 Vac maximum) is available on the terminal of the heating control

unit (terminals 

14

15

and 

16

).

• Tripping of the contact indicates:

- tripping of the heater's thermal safety thermostat,
- undervoltage on the heating power circuit,
- a drop in tank water pressure.

Detail of control connections:

E

F

KM3

40

32 33

41

30 31 32 33

12 3 4

6

89

7

KM2

8

12 13

9

E

B

C

D

B1

S1

Printed Circuit

Board

6.5.5 - SUPPLEMENTARY ELECTRIC HEATING OPERATION

PRESENTATION

• The heater consists of resistance each rated at 8 kW (400 V, 3-phase), secured to the buffer tank.
• Backup is authorized with the 2nd stage, although is triggered only if the generator is out of service.

Securities:

- One of the resistance is equipped with a 2-threshold safety thermostat: one automatic reset threshold which is factory

set at 70°C and a manual reset set at 87°C. 

- All malfunctions detected by this thermostat results in the shut-

down of the electric heating.

- After having turned off (and locked out) the power to the unit

and corrected the malfunction, the safety device is reset by
pressing the button located on the body of the thermostat. This
thermostat is accessible under the resistance’s head cover.

- This heater is also slaved to the operation of the water

circulating pump and to the water pressure switch installed on
the tank.

- These heating elements are controlled from a specific heating

control unit (see location in paragraph 4.2.3), equipped with a
2-stage electronic controller.

1

st

stage - 8 kW

2

nd

stage - 8 kW

Back-up - 8 kW

Security

PHRV 22 to 36

Tank

Heating power:

24 kW

Current:

35 A

UNIT

Electrical box

TANK

Unit 

On/Off

Heat/Cool
inversion

Pump 

control

Supplementary

heating

authorization

3

rd

stage

authozisation

Electronic

controller

Water 
temperature 
sensor (installation return)

Heating control electrical box

Содержание PHRV 22

Страница 1: ...zione idronica incorporata aria acqua Fluido refrigerante R 407 C Bomba de calor con equipamiento hidr ulico aire agua Fluido refrigerante R 407 C W rmepumpen reversibel mit hydraulikausr stung Luft W...

Страница 2: ...407 C Fluid R 407 C as opposed to R22 is not a pure fluid but a blend composed of 23 R 32 25 R 125 52 R 134 A The compressors approved for operation with this fluid are filled beforehand with polyalc...

Страница 3: ...sound insulation Resistance case WATER EXCHANGER Plate water exchanger with heat insulation AIR EXCHANGER Thin plate air exchanger with protective grille ELECTRIC FAN UNIT Electric fan unit with prot...

Страница 4: ...36 b a 40 975 G G 125 1050 c 290 LP Manometer Accessory HP Manometer Accessory 4 22 5 mm holes for sling attachment Net weight PHRV 22 303 kg PHRV 25 305 kg PHRV 32 327 kg PHRV 36 363 kg Net weight T...

Страница 5: ...points the unit must be installed outside in an appropriate location and in compliance with environmental requirements sound level integration etc the unit s installation location must be perfectly l...

Страница 6: ...od No 41 No other power cable Ambient temperature 40 C The lengths indicated below correspond to a voltage drop less than 5 in the cable The complete electrical specifications are given in the table o...

Страница 7: ...oling the function is activated by special parameterisation see paragraph 5 8 access to parameters in combination with button 1 3 LED display 4 Cooling mode indicator 5 Heating mode indicator 6 Compre...

Страница 8: ...lamp 6 goes out and the operating mode indicator lamps 4 and 5 flash the unit s circulating pump remains in operation Complete stop the unit can be completely stopped with the circulating pump shut d...

Страница 9: ...re accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm active Set val...

Страница 10: ...erious malfunctions Go to the PSS section in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Display the password 199 using buttons 1 and 2 and validate it by simultaneou...

Страница 11: ...SD3 rises above the end of frosting temperature threshold The defrosting phase is indicated by the steady illumination of indicator lamp 7 Note The ventilation can restart after defrosting is complete...

Страница 12: ...g sequence stand by cooling heating stand by The stand by mode is indicated by the extinction of the heating and cooling mode indicator lamps Pre ventilation generally speaking in order to condition t...

Страница 13: ...de temperature Set point Set point Example Factory setting in heating mode Factory setting in cooling mode Condensation pressure control device The unit is equipped with a separate condensation pressu...

Страница 14: ...e taps while observing the following precautions 6 3 REMOTE CONTROL Code 70250055 The functions and display are exactly the same as those on controller The only difference concerns the buttons and whi...

Страница 15: ...nal strip Connect the ribbon cable supplied between the interface and the ECH controller Connect the interface s 230 VAC power supply to the output of breaker Q4 using the Blue and Black wires supplie...

Страница 16: ...in cases where the tank is placed underneath the unit The pipes must be at a sufficient distance from the removable panels to enable servicing operations to be performed Make the connection with flexi...

Страница 17: ...le copper cable with PR insulation Installation in non ventilated cable duct installation method No 41 No other power cable Ambient temperature 40 C The lengths indicated below correspond to a voltage...

Страница 18: ...nections E F KM3 40 32 33 41 30 31 32 33 1 2 3 4 6 8 9 7 KM2 8 12 13 9 E B C D B1 S1 Printed Circuit Board 6 5 5 SUPPLEMENTARY ELECTRIC HEATING OPERATION PRESENTATION The heater consists of resistance...

Страница 19: ...over of the controller s front panel 30 31 U N 32 33 1 2 10 13 3 4 S1 5 6 11 R1 R2 GR Chaud Heat Froid Cool 5 6 7 3 4 8 10 1 2 9 36 39 33 42 30 45 14 16 12 18 10 20 29 31 27 33 25 35 DL3 DL4 DL5 DL2 D...

Страница 20: ...ater circulation pump 5 min and the immediate shutdown of the unit and auxiliary stages The corresponding indicator lights are thus off D COOLING MODE With the remote mode inversion contact being open...

Страница 21: ...c pressure gauge Use the circulating pump curves in paragraph 10 to determine the water flow rate Note The generator s water output must be ensured at all times particular attention should be paid in...

Страница 22: ...n given in the case of a tank with supplementary heating different power supplies Any work must be carried out by personnel qualified and authorised to work on this type of machine Prior to all mainte...

Страница 23: ...P H R V 2 2 4 2 1 m 3 h P H R V 2 5 4 6 8 m 3 h P H R V 3 2 5 9 4 m 3 h P H R V 3 6 7 2 0 m 3 h GB 23 10 CIRCULATING PUMP CURVES PHRV 22 25 Water flowrate m3 h Manometric delivery head of the pump kP...

Страница 24: ...5 C 35 C 45 C 4 5 0 1 2 3 4 5 6 7 6 7 8 9 10 11 12 13 14 15 25 C 15 C 35 C 45 C HIGH PRESSURE LOW PRESSURE PHRV 22 PHRV 25 PHRV 32 PHRV 36 Water outlet temperature C Low pressure relative bar Outside...

Страница 25: ...25 PHRV 32 PHRV 36 Outside wet bulb temperature C Low pressure relative bar Water outlet temperature C Outside wet bulb temperature C High pressure relative bar Water outlet temperature C Outside wet...

Страница 26: ...erature setpoint Heating Cooling Water temperature control sensor positioned in Inlet Outlet TEMPERATURES C PRESSURES bar Outside temperature Water type Pure Glycol Glycol Water inlet generator Water...

Страница 27: ...cation 0 14 num 0 H52 Temperature measurement unit C F 0 1 flag 0 H54 Parameter list No 0 999 num depending on the model H55 Parameter list index 0 999 num depending on the model H57 Alarm relay activ...

Страница 28: ...ioramento dei nostri prodotti ci riserviamo di modificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verb...

Отзывы: