background image

GB

10

5.6.3 - SETPOINT ADJUSTMENT

• Simultaneously press buttons (

1

) and (

2

) for at least 2 seconds, "

SET

" is displayed.

• Press the 2 buttons again, "

Coo

" is displayed. Using button (

1

) or (

2

), display either "

HEA

" or "

Coo

" corresponding to

the heating setpoint ("

HEA

") or cooling setpoint ("

Coo

").

• Simultaneously press the 2 buttons again for 2 seconds. The setpoint value appears. If needed, modify the value with

the buttons. 

• Press the 2 buttons simultaneously to validate the setpoint.
• Return to the normal display by simultaneously pressing the 2 buttons for more than 2 seconds.

Reminder: control on the installation return temperature.

Note:
All units are factory configured and parameterized for optimum operation in the terminal unit application.

5.6.4 - DISPLAY OF TEMPERATURES, ALARMS, AND HOUR COUNTERS

Accessible directly via the menu, see diagram 5.6.2.
• Temperatures "

TP

:

Displays the values indicated by each temperature probe: 

t01

: water inlet temperature.

t02

: water outlet temperature.

t03

: exchanger air temperature.

t04

: outside air temperature.

• Alarms "

Err

":

Displays the list of all current alarms (scroll through the alarm messages with buttons (

1

) and/or (

2

)).

• Hour counters "

OHr

":

Displays the operating time of the compressor ("

OH1

") and the circulating pump ("

OHP

"). The counter can be reset by a

long press (> 2 seconds) on button (

1

) when the counter value is displayed.

5.6.5 - ACCESS TO THE TECHNICAL PARAMETERS "PAR"

For qualified personnel after entering the password "PSS". Any incorrect adjustment may lead to serious
malfunctions.

• Go to the "

PSS

" section in the menu. Briefly and simultaneously press buttons (

1

) and (

2

). The "

---

" message appears.

Display the password ("

199

")  using buttons (

1

) and (

2

) and validate it by simultaneously pressing buttons (

1

) and (

2

). It

is now possible to enter the parameters section "

PAr

".

CAUTION: 
After modifying one or more technical parameters, the controller must be turned off then back on again to reset
it with its new parameters.

5.7 - ALARMS

• When an alarm occurs:

- the alarm report is activated,
- the corresponding code flashes on the display unit. See table,
- the unit stops if necessary (see table below).

• Remedy the fault.

IMPORTANT NOTE: 
All work must be carried out by qualified, experienced personnel.

• The alarms are normally reset automatically.

CAUTION

: the alarms:

- HP, 
- LP (low pressure), 
- Anti-freeze,
- Water flow rate 

have an event counter that shifts to 

manual

reset if the alarm occurs several times during the last hour.

• The "refrigerating circuit" alarm is reset manually.
• The alarms are reset by briefly pressing the "

ON/OFF

" button (

1

).

• When the alarm is cleared:

- the alarm report is de-activated,
- the display reverts to normal (not flashing),
- the machine can re-start (if it was stopped).

• Special features of the alarm relay:

- the potential-free change-over contact (2 A - 230 VAC max.), on the terminal strip of the PCB, comes from the relay

located on this board,

-  the relay is actuated in the absence of an alarm (contacts: 5/6 closed and 5/7 open),
- in the case of alarm or power supply loss, the relay is released (contacts: 5/6 open and 5/7 closed).

Factory setting

(terminal units)

HEA

Heating set point

4 0

°C

25 to 45°C

Coo

Cooling set point

1 2

°C

9 to 25°C

Parameters

Code

Adjustment range

Содержание PHRV 22

Страница 1: ...zione idronica incorporata aria acqua Fluido refrigerante R 407 C Bomba de calor con equipamiento hidr ulico aire agua Fluido refrigerante R 407 C W rmepumpen reversibel mit hydraulikausr stung Luft W...

Страница 2: ...407 C Fluid R 407 C as opposed to R22 is not a pure fluid but a blend composed of 23 R 32 25 R 125 52 R 134 A The compressors approved for operation with this fluid are filled beforehand with polyalc...

Страница 3: ...sound insulation Resistance case WATER EXCHANGER Plate water exchanger with heat insulation AIR EXCHANGER Thin plate air exchanger with protective grille ELECTRIC FAN UNIT Electric fan unit with prot...

Страница 4: ...36 b a 40 975 G G 125 1050 c 290 LP Manometer Accessory HP Manometer Accessory 4 22 5 mm holes for sling attachment Net weight PHRV 22 303 kg PHRV 25 305 kg PHRV 32 327 kg PHRV 36 363 kg Net weight T...

Страница 5: ...points the unit must be installed outside in an appropriate location and in compliance with environmental requirements sound level integration etc the unit s installation location must be perfectly l...

Страница 6: ...od No 41 No other power cable Ambient temperature 40 C The lengths indicated below correspond to a voltage drop less than 5 in the cable The complete electrical specifications are given in the table o...

Страница 7: ...oling the function is activated by special parameterisation see paragraph 5 8 access to parameters in combination with button 1 3 LED display 4 Cooling mode indicator 5 Heating mode indicator 6 Compre...

Страница 8: ...lamp 6 goes out and the operating mode indicator lamps 4 and 5 flash the unit s circulating pump remains in operation Complete stop the unit can be completely stopped with the circulating pump shut d...

Страница 9: ...re accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm active Set val...

Страница 10: ...erious malfunctions Go to the PSS section in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Display the password 199 using buttons 1 and 2 and validate it by simultaneou...

Страница 11: ...SD3 rises above the end of frosting temperature threshold The defrosting phase is indicated by the steady illumination of indicator lamp 7 Note The ventilation can restart after defrosting is complete...

Страница 12: ...g sequence stand by cooling heating stand by The stand by mode is indicated by the extinction of the heating and cooling mode indicator lamps Pre ventilation generally speaking in order to condition t...

Страница 13: ...de temperature Set point Set point Example Factory setting in heating mode Factory setting in cooling mode Condensation pressure control device The unit is equipped with a separate condensation pressu...

Страница 14: ...e taps while observing the following precautions 6 3 REMOTE CONTROL Code 70250055 The functions and display are exactly the same as those on controller The only difference concerns the buttons and whi...

Страница 15: ...nal strip Connect the ribbon cable supplied between the interface and the ECH controller Connect the interface s 230 VAC power supply to the output of breaker Q4 using the Blue and Black wires supplie...

Страница 16: ...in cases where the tank is placed underneath the unit The pipes must be at a sufficient distance from the removable panels to enable servicing operations to be performed Make the connection with flexi...

Страница 17: ...le copper cable with PR insulation Installation in non ventilated cable duct installation method No 41 No other power cable Ambient temperature 40 C The lengths indicated below correspond to a voltage...

Страница 18: ...nections E F KM3 40 32 33 41 30 31 32 33 1 2 3 4 6 8 9 7 KM2 8 12 13 9 E B C D B1 S1 Printed Circuit Board 6 5 5 SUPPLEMENTARY ELECTRIC HEATING OPERATION PRESENTATION The heater consists of resistance...

Страница 19: ...over of the controller s front panel 30 31 U N 32 33 1 2 10 13 3 4 S1 5 6 11 R1 R2 GR Chaud Heat Froid Cool 5 6 7 3 4 8 10 1 2 9 36 39 33 42 30 45 14 16 12 18 10 20 29 31 27 33 25 35 DL3 DL4 DL5 DL2 D...

Страница 20: ...ater circulation pump 5 min and the immediate shutdown of the unit and auxiliary stages The corresponding indicator lights are thus off D COOLING MODE With the remote mode inversion contact being open...

Страница 21: ...c pressure gauge Use the circulating pump curves in paragraph 10 to determine the water flow rate Note The generator s water output must be ensured at all times particular attention should be paid in...

Страница 22: ...n given in the case of a tank with supplementary heating different power supplies Any work must be carried out by personnel qualified and authorised to work on this type of machine Prior to all mainte...

Страница 23: ...P H R V 2 2 4 2 1 m 3 h P H R V 2 5 4 6 8 m 3 h P H R V 3 2 5 9 4 m 3 h P H R V 3 6 7 2 0 m 3 h GB 23 10 CIRCULATING PUMP CURVES PHRV 22 25 Water flowrate m3 h Manometric delivery head of the pump kP...

Страница 24: ...5 C 35 C 45 C 4 5 0 1 2 3 4 5 6 7 6 7 8 9 10 11 12 13 14 15 25 C 15 C 35 C 45 C HIGH PRESSURE LOW PRESSURE PHRV 22 PHRV 25 PHRV 32 PHRV 36 Water outlet temperature C Low pressure relative bar Outside...

Страница 25: ...25 PHRV 32 PHRV 36 Outside wet bulb temperature C Low pressure relative bar Water outlet temperature C Outside wet bulb temperature C High pressure relative bar Water outlet temperature C Outside wet...

Страница 26: ...erature setpoint Heating Cooling Water temperature control sensor positioned in Inlet Outlet TEMPERATURES C PRESSURES bar Outside temperature Water type Pure Glycol Glycol Water inlet generator Water...

Страница 27: ...cation 0 14 num 0 H52 Temperature measurement unit C F 0 1 flag 0 H54 Parameter list No 0 999 num depending on the model H55 Parameter list index 0 999 num depending on the model H57 Alarm relay activ...

Страница 28: ...ioramento dei nostri prodotti ci riserviamo di modificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verb...

Отзывы: