8
GB
3.2 INSTALLATION OF THE SUPPORT PLATE
Support plate
cover
50
30
360
30
60
Guide arrows
20
105
75
20
35
155
380
760
MW 2
MW 3
800
80 mm dia. hole
32
D
F
Ø 5
E
1 000
60
360
38
Hole Ø 80 mm
Guide arrows
MW 4
MW 5
A- After deciding on the position of the internal unit, position the support plate according
to the overall dimensions of the unit and referring to the measurements on the drawing
opposite.
B- Mark and dot punch the six 5 mm dia. fixing holes.
C- Make the hole for the pipes (see § 4.2):
- either by removing the cover (see sketch) for pipes entering through the side,
- or by positioning the 80 dia. hole (lining up on the arrow) and by making it (see
3.3) for pipes entering through the rear of the handler.
D- Drill the six 32 mm deep, 5 mm dia. fixing holes.
E - Put the 6 plugs in the 5 mm dia. holes.
F - Fix the support plate on the wall using the six 4 x 16 screws.