GB
5
P
Q
Q
P
A BUS
BUS
BUS
Control box
With built-in ambient temperature sensor.
To be installed in zone 1.
Water
temperature,
zone 2
Heating
board
2-ZONE FLOOR MODULE
Water
temperature,
zone 1
Ambient
temperature,
zone 2
Ambient
temperature,
zone 1
Board, zone 2
A2
Board, zone 1
A1
Possible accessory
70250065
(If control box is installed
outside zone 1)
A BUS
- 2-conductor cable, min. size 1 mm
2
.
-
Total
length of the BUS connection: 40 meters (heating board / control box conn heating board / zone board if
any connection).
- To be connected on the terminal strip of the boards, zones
A1
and
A2
, located in the module.
A2
A1
Heating
board
Caution:
Be sure to respect
the pola and -
P Zone ambient temperature sensor
- For zone 2, Floor: mandatory, supplied with the module.
- For zone 1, Floor: required only if the control unit is not placed in a
location that is representative of the temperature in zone 1.
Caution
:
In this case, the remote zone 1 sensor must be activated through
parameterisation on the control unit (refer to control’s technical manual).
This sensor is proposed as accessory
70250065
.
- Wall mounting: the sensor is designed to be mounted in a "Mosaïc" type
(45 x 45), flush-mounted electrical box (not supplied).
It is to be installed in a location that is representative of the temperature
in the zone.
- The sensor must not be installed in corners, on shelves or behind
curtains, near sources or heat or directly exposed to sunlight.
The unit should be installed approximately 1.5 m above the floor.
- Use a 2-conductor cable for installation, minimum size: 0.5 mm
2
and max. length: 25 meters.
- To be connected directly on the corresponding zone board (terminals
C
and
S5
).
Q Water temperature probe (Floor zone outgoing line)
- Indicated for informational purposes as it is already connected in the module.
1.50 m
20 cm min.
Ambient Sensor
HEATING MODULE
2-ZONE FLOOR MODULE
HEATING MODULE