background image

User Notice

The total capacity of the indoor units which runs at the same time can not exceed 150% of 

that of the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be poor.

Switch the main power on 8 hours before starting the unit, helpful for a successful startup.

It is a normal phenomenon that the indoor unit fan will still run for 20~70 seconds after the 

indoor unit receives the “stop” signal so as to make full use of after-heat for the next operation.

When the running modes of the indoor and outdoor units conflict, it will be indicated on 

the display of the wired controller in five seconds and then the indoor unit will stop. In this case, 

they can back to the normal condition by harmonizing their running modes: the cooling mode is 
compatible with the dehumidifying mode and the fan mode can go with any other mode. If the 
supply power fails when the unit is running, then the indoor unit will send the “start” signal to the 
outdoor unit three minutes later after power recovery.

Do not frequently power on/off the unit, otherwise it would cause the compressor, fan, 

mainboard, electrostatic expansion valve, or other important component damaged, and then make 
the unit fail.

During installation, the communication cable and the power cord must not be twisted 

together but instead separated with an interval of at least 2cm; otherwise the unit is likely to run 
abnormally.

Cautions for the Debugging and Maintenance Personnel

.

During debugging and maintenance, prior to the startup of the compressor make sure the 

heating belt of the compressor has been energized for at least eight hours! Once the compressor is 
started, it must be guaranteed that it works continuously for at least 30 minutes, otherwise it would 
be damaged!

This series outdoor units are matched with the free match D.C.inverter Muti-variable 

air conditioner indoor unit under the same working conditons exported to European 
Union.

This product must not be disposed together with the domestic waste. This product has to be 

disposed at an authorized place for recycling of electrical and electronic appliances.

Содержание GRFMX366R5I

Страница 1: ...u for choosing Commercial Air Conditioners please read this manual carefully before operation and retain it for future reference GRFMX366R5I MAFX96R5I MAFX126R5I MAFX186R5I MAFX246R5I OUTDOOR UNITS IN...

Страница 2: ...u for choosing Commercial Air Conditioners please read this manual carefully before operation and retain it for future reference GRFMX366R5I MAFX96R5I MAFX126R5I MAFX186R5I MAFX246R5I OUTDOOR UNITS IN...

Страница 3: ...to the outdoor unit three minutes later after power recovery Do not frequently power on off the unit otherwise it would cause the compressor fan mainboard electrostatic expansion valve or other impor...

Страница 4: ...6 2 4 Refrigerant Charging and Trial Running 9 3 Working Principles of the Unit 12 4 Parts and Components of the Unit 13 5 Maintenance 14 5 1 Check before the Seasonal Use 14 5 2 Check after the Seaso...

Страница 5: ...le Please take notice of the supporting frame of the unit to see if it is damaged over the long time period of use Never refit the unit and contact the sales agent or the professional installation per...

Страница 6: ...nimize the length and bends of the refrigerant pipe 3 Do not install the outdoor unit under the window or between the buildings to prevent the normal running noise entering the room 4 Where the flow o...

Страница 7: ...ned based on the maximum power maximum amps of the unit The specifications of the power cable listed in the table above are applied to the conduit guarded multi wire copper cable like YJV copper cable...

Страница 8: ...stalled on the base frame which is stable and secure uncouth to withstand the weight of the unit otherwise it would incur vibration and noise 3 During the installation a consideration should be taken...

Страница 9: ...lifting the unit and protect the unit carefully during lifting to prevent damaging the mental sheet which would result in rusting in future 5 The unit should be installed where there is as little as...

Страница 10: ...installed on a concrete base frame with a height of 10cm 5 The installation space of the unit should be as required in Fig 6 Installation Space Requirements of the Outdoor Unit 36K 42K Fig 6 2 3 Conne...

Страница 11: ...ax Length for Single Unit m 20 25 LX Max installation altitude Outdoor unit and indoor unit 15 15 H1 Indoor unit and indoor unit 7 5 7 5 H2 Table 4 Dimension of the Refrigerant Pipe of the Indoor Unit...

Страница 12: ...ed by brackets that is don t let the unit withstand the weight of it CAUTION For the free match D C inverter Muti variable air conditioner unit each pipe should be labeled to tell which system it belo...

Страница 13: ...charged into the refrigerant pipe during the field installation 2 Check if the liquid valve and the gas valve of the outdoor unit are closed fully 3 As shown in the following figure Fig 9 expel the ga...

Страница 14: ...m 3 Example 42K a b c d e Fig 10 Table 8 Indoor Unit Serial No Model Indoor Unit Ducted Type GFH 09 EA K3DNA1A I Indoor Unit Ducted Type GFH 09 EA K3DNA1A I Indoor Unit Ducted Type GFH 09 EA K3DNA1A I...

Страница 15: ...shock Does the wire meet the regulated requirement The unit may break down or the component may be burnt out Is there any obstacle at the air inlet outlet of the indoor outdoor unit The cooling heati...

Страница 16: ...air and then is turned into refrigerant liquid After passing through the throttling device the temperature and pressure of the refrigerant liquid will further decrease and then go the main valve Afte...

Страница 17: ...iable air conditioner unit one outdoor unit is able to drive up to four or five indoor units which can be cassette type duct type wall mounted or floor ceiling type Among them the cassette type and th...

Страница 18: ...vent combustion or deformation 5 1 Check before the Seasonal Use 1 Check if the inlet outlet of the indoor outdoor unit is clogged 2 Check if the earth lead is earthed reliably 3 Check if the batterie...

Страница 19: ...the power supply properly Insufficient batteries voltage of the remote controller Change new batteries Remoter controller out of the control scope Keep the control distance within 8 meters The unit st...

Страница 20: ...e unit squeaks when it is in and after the running It is the sound of frication generated by the skin plate etc which swells due to the temperature change The unit blows out dust When the unit restart...

Страница 21: ...Error Hc Flash 6 times Hc Hc Drive Error Startup Failure Lc Flash 11 times Lc Lc Drive Error DC Fan motor Error LA Outdoor No indoor fan motor H6 Flash 11 times Indoor Compressor phase circuit detecti...

Страница 22: ...ive Error Unit communication error See Table 16 Flash 6 times E6 E6 Indoor Unit n indoor pipe midway temperature sensor error See Table 16 Flash twice E2 E2 Indoor Indoor Evaporator Temp Sensor Short...

Страница 23: ...h 3 times H3 H3 Drive Error IPM Protection H5 Flash 5 times H5 H5 Drive Error Motor Desynchronizing H7 Flash 7 times H7 H7 Drive Error PFC Error Hc Flash 6 times Hc Hc Drive Error Startup Failure Lc F...

Страница 24: ...re sensor error 33 Unit C indoor unit pipe outlet temperature sensor error 14 Unit A indoor pipe inlet temperature sensor error 24 Unit B indoor pipe inlet temperature sensor error 34 Unit C indoor pi...

Страница 25: ...Refer to the real products for the exact position of each component Once errors are displayed on the controller please shut off the air conditioning unit and contact the professionally skilled person...

Страница 26: ...ignal from the wireless controller or it has run for ten minutes Forcible Defrosting How to activate this function when indoor unit runs under the HEAT mode and at 16 it will activate the forcible def...

Страница 27: ...5 24 Max cooling 32 23 48 26 Min cooling 21 15 18 Rated Heating 20 15 7 6 Max heating 27 24 18 Min heating 20 15 15 16 Notes The heating cooling capacity and noise listed below are all measured before...

Страница 28: ...fluorinated greenhouse gas with global warming potential GWP 2087 50 Do not release R410A into the atmosphere Technibel is a TRADE mark of NIBE ENERGY SYSTEMS FRANCE used under licence IMPORTED DISTR...