– 50 –
3. ELECTRICAL DATA
Cooling:
Rating Conditions : Indoor Air Temperature 27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions : Indoor Air Temperature 35
°
C DB / 25
°
C WB
Outdoor Air Temperature 45
°
C DB
Heating:
Rating Conditions : Indoor Air Temperature 20
°
C DB
Outdoor Air Temperature 7
°
C DB / 6
°
C WB
Full Load Conditions : Indoor Air Temperature 27
°
C DB
Outdoor Air Temperature 21
°
C DB / 15.5
°
C WB
●
Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 – 415 V / 3 phase / 50 Hz
Rating conditions
A 0.43 / 0.43 0.62 / 0.65 4.46 / 4.08 4.8 / 4.43
kW 0.09 / 0.10 0.13 / 0.15 2.50 / 2.52 2.72 / 2.77
Full load conditions
A 0.43 / 0.43 0.62 / 0.65 4.98 / 4.57 5.33 / 4.93
kW 0.09 / 0.10 0.13 / 0.15 2.85 / 2.89 3.07 / 3.14
Starting amperes A 1 / 1 1 / 1 24 / 27 26 / 29
●
Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 0.33 / 0.34 0.62 / 0.65 4.63 / 4.40 4.94 / 4.72
kW 0.07 / 0.08 0.13 / 0.15 2.61 / 2.63 2.81 / 2.85
Full load conditions
A 0.33 / 0.34 0.62 / 0.65 5.40 / 4.94 5.71 / 5.26
kW 0.07 / 0.08 0.13 / 0.15 3.02 / 3.05 3.22 / 3.28
Starting amperes A 1 / 1 1 / 1 24 / 27 26 / 29
Indoor model : SPA250R5TAA / Outdoor model : GR250R7TAA
3-1 Electrical characteristics