– 49 –
3. ELECTRICAL DATA
Cooling:
Rating Conditions : Indoor Air Temperature 27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions : Indoor Air Temperature 35
°
C DB / 25
°
C WB
Outdoor Air Temperature 45
°
C DB
Heating:
Rating Conditions : Indoor Air Temperature 20
°
C DB
Outdoor Air Temperature 7
°
C DB / 6
°
C WB
Full Load Conditions : Indoor Air Temperature 27
°
C DB
Outdoor Air Temperature 24
°
C DB / 15.5
°
C WB
●
Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 220 – 240 V / 1 phase / 50 Hz
Rating conditions
A 0.43 / 0.43 0.62 / 0.65 13.68 / 13.92 14.73 / 15.00
kW 0.09 / 0.10 0.13 / 0.15 2.89 / 2.95 3.11 / 3.20
Full load conditions
A 0.43 / 0.43 0.62 / 0.65 15.78 / 15.72 16.83 / 16.80
kW 0.09 / 0.10 0.13 / 0.15 3.36 / 3.42 3.58 / 3.67
Starting amperes A 1 / 1 1 / 1 66 / 72 68 / 74
●
Heating
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 220 - 240 V / 1 phase / 50 Hz
Rating conditions
A 0.33 / 0.34 0.62 / 0.65 13.81 / 14.03 14.76 / 15.02
kW 0.07 / 0.08 0.13 / 0.15 2.91 / 2.97 3.11 / 3.20
Full load conditions
A 0.33 / 0.34 0.62 / 0.65 15.11 / 14.83 16.06 / 15.82
kW 0.07 / 0.08 0.13 / 0.15 3.13 / 3.22 3.33 / 3.45
Starting amperes A 1 / 1 1 / 1 66 / 72 68 / 74
Indoor model : SPA250R5TAA / Outdoor model : GR250R5TAA