As standard configuration the air conditioner operates detecting the room temperature through the sensor
equipped in the wireless remote controller (icon I FEEL shown on the display). This feature provides a
personalised environment since the temperature can be detected where the remote controller is located.
It is possible to de-activate this option pressing the I FEEL button on the remote controller.
In this case the I FEEL icon is no longer displayed and room temperature is detected through the sensor
included in the indoor unit.
6-8 NIGHT Function
When this function is active, room temperature changes automatically to compensate for body temperature
variations while sleeping. After 10 hours of operation system switches automatically to OFF state.
This mode of operation is available both in COOLING and HEATING mode.
6-9 DRAIN PUMP
Pump operates when the unit is running in COOLING and DRY modes.
The level detection is done through a float switch connected at the input FS (closed under normal condition,
and opened when water overflow). System operation is according to the following chart:
30sec
30sec
20sec
20sec
FS
Contact