Model: TX-203,TX-204,TX-228; Article No. 5021,5023,5040; 10/2022 

6. Measure the voltage of the solar panel to the micro inverter with a suitable multi-
meter. The required starting voltage of the micro inverter is above DC22V. 
7. Check the MC4 connectors of the micro inverter and solar panel(s). Damaged DC 
connections must be replaced.  
8. If necessary, check with your grid operator whether the grid frequency matches the 
frequency range of the micro inverter. 

CAUTION!  

Do not attempt to repair the micro inverter. 
If  the  above  steps  do  not  solve  the  problem,  contact  our  support  or  an 
electrician. 
The AC connection on the micro inverter cannot be replaced/repaired. If the 
cable has been damaged, the device should be disposed of. 

Unless otherwise specified, maintenance work must be carried out with the 
equipment disconnected from the mains (mains switch open) and the solar 
panels covered, or insulated. 

Do not use rags or corrosive products for cleaning that could corrode parts 
of the equipment or cause electrostatic charges. 

Avoid temporary repairs. All repairs should be made only with original spare 
parts. 

Each micro inverter should be protected by a circuit breaker, but central 
disconnect protection is not required unless specified by national standards, 
or by the responsible network operator. 

Technical specifications 

 Verify that the voltage and current specifications of the solar panels match 

those of the micro inverter. 

 The maximum open circuit voltage of the solar panel must be within the 

operating voltage range of the micro inverter. 

 It is recommended that the maximum rated current in the MPP be equal to 

or  less  than  the  maximum  input  DC  current.  However,  the  maximum  short 
circuit  current  must  be  equal  to  or  less  than  the  maximum  DC  input  short 
circuit current. 

It is NOT recommended to oversize the output DC power of the solar panels 

by more than 1.35 times (based on the AC output power of the micro inverter). 

 
For the technical specifications of the solar module, please refer to the enclosed data 
sheet. 

Inverter 

Modell 

TX-212 

TX-220/228 

DC-input 

Recommended panel power (W) 

240-380 (per panel) 

Panel compatibility 

60-cell or 72-cell panels 

Содержание TX-212

Страница 1: ...physical sensory or mental capacities or by persons lacking in experience or knowledge unless they are supervised or instructed on the use of this device by a person responsible for their safety Chil...

Страница 2: ...on 9 Requirements for the operation of a photovoltaic system 9 Connecting the micro inverter 9 Mounting 11 General hints 11 Balcony 11 Flat roof bitumen roof 11 Facade 12 Connect the solar panels DC c...

Страница 3: ...Specifications subject to change without notice please make sure you are using the latest manual available on the manufacturer s website ATTENTION According to the German Federal Network Agency instal...

Страница 4: ...ion on the microinverter and on the solar modules The device may only be used for its intended purpose in accordance with this user manual Observe the safety instructions during use Before commissioni...

Страница 5: ...n a low height Keep the product away from extreme heat Never immerse the product in water or other liquids Technical changes and errors excepted Warning Do not install the device if the AC cable of th...

Страница 6: ...ss and have received confirmation approval from the electricity network operator If you mount the micro inverters at a great height avoid possible fall risks Do not insert electrically conductive part...

Страница 7: ...able responsible for any direct indirect punitive incidental special consequential danger to property or life improper storage whatsoever arising out of or connected with the use or misuse of their pr...

Страница 8: ...r 1x AC input end cap 1x connection cable 1x user manual Prduct overview PV Micro Inverter 300W TX 203 1 Betteri socket input 230V AC 4 Betteri plug output 230V AC 2 Mounting hole 5 Input solar panel...

Страница 9: ...ement required A bi directional meter must be present or depending on what your electricity provider specifies Simple electricity meters are often not sufficient If necessary the consent of the landlo...

Страница 10: ...breaker but keeping the protective grounding conductor in the branch circuit breaker connected to the micro inverter Then disconnect the DC inputs CAUTION Do not under any circumstances connect the DC...

Страница 11: ...he photovoltaic system can be installed up to a roof height of 9m a sea level of max 350 m and a roof pitch of 45 We recommend a distance of 1 25 m to fire walls of adjacent buildings e g row houses F...

Страница 12: ...The connectors of some solar panels have the polarity printed on them which is valid for the panels The DC cable of the micro inverter with the plus marking is connected to the pole of the panel the n...

Страница 13: ...need to produce at least a start voltage of 22V Initial state 1 The micro inverter is connected to the solar panels 2 The microinverter is connected to the house mains via Wieland plug recommended or...

Страница 14: ...d grid exceeds falls below the voltage frequency range of the micro inverter If the LED shows no function or remains OFF the most common cause is that there is no connection to the solar panel or the...

Страница 15: ...the equipment or cause electrostatic charges Avoid temporary repairs All repairs should be made only with original spare parts Each micro inverter should be protected by a circuit breaker but central...

Страница 16: ...under 50Hz 220 V 230 V 55 65 under 60Hz 220 V 230 V Power factor 0 99 standard 0 8 leading 0 8 delayed Output current harmonic distortion 3 Maximum number of devices in series 12 6 Efficiency safety a...

Страница 17: ...overloading of the cables in the household they are protected by a line circuit breaker LSS This switches off automatically as soon as an overload occurs As a rule several sockets and consumers are pr...

Страница 18: ...16A circuit breaker 0 5 1 5 5 7 Maximum rated current Ig of the power generation system with 13A circuit breaker 3 5 4 5 8 10 Photovoltaic system one solar module two solar modules up to 3 115W from...

Страница 19: ...5W In the example right half of the picture the power of the mini solar system is 2 6A 600W which complies with the permissible load Further safety instructions Only connect the mini solar system to a...

Страница 20: ...of old devices that can no longer be used separately from household waste e g at a collection point in his or her municipality or district This ensures that the old devices are properly recycled and t...