BK Mikro 7 Manual
OI: BK MIKRO 7
Page 14
Rev. 2.00 dated 20.01.2006
Selection inputs
•
"S1" terminal
"S2" terminal
"S3" terminal
The input signal (static) of +24 VDC relative to "Com" terminal must be stable during 10 ms min.
before "Teach" or "Start".
The input S3 must be connected at a wand length of 250 mm. Concerning shorter wands, S3
remains unconnected. By connecting S3, the wand is slower and therefore it oscillates less.
S1/S2 selection inputs determine scanning direction !
The direction of scanning depends on connected scanner with corresponding switch position.
The meaning of "Clockwise/Counter-clockwise" toggle switch position on control unit may be
changed by corresponding S1/S2 input signals.
S1 and S2 may be open. Then is: S1=0, S2=0.
Scanner BK7SC
Scanner BK7RLSC
S1
S2
„CW/CCW“
Scanning
Scanning
Default setting
è
0
0
R
CW
CW -CCW
0
0
L
CCW
CCW-CW
1
0
R
CW
CW
2)
1
0
L
CW
1)
CW
1)
2)
0
1
R
CCW
1)
CCW
1)
2)
0
1
L
CCW
CCW
2)
1
1
R
CCW
1)
CCW-CW
1)
1
1
L
CW
1)
CW -CCW
1)
Note:
Default setting: S1 and S2 are not connected.
1)
Scanning direction differs from "CW/CCW" switch setting:
S1/S2 inputs change meaning of toggle switch.
2)
Stop position must be defined by a “Teach-in” in both directions or by a
reference procedure in both directions. Missing stop position causes an error
message, and pulses on control inputs are ignored.