TechGrow Ballast Basic Micro Скачать руководство пользователя страница 14

____________________________________________________________________________________________________________________________ 
                 
 
              

Tech

Grow

 | Innovative Growing Solutions                

              14 

 

1. Installation 

 
1.

 

Mount the Ballast Connect Micro to the wall using 
the included mounting kit. 

2.

 

If desired, connect a Temp Probe to the bottom of 
the Ballast Connect Micro. 

3.

 

First

, put the plugs of the lamps in the outlets of 

the Ballast Connect Micro. 

4.

 

After that

, connect the plug of the Ballast Connect 

Micro to a 230V outlet (minimum 10A). 

5.

 

Ready! 

 

ATTENTION: NEVER plug a lamp into the Ballast 

Connect Micro and NEVER remove a lamp’s plug 

from the Ballast Connect Micro when the relays 
(sockets) are on. You may only connect or 
disconnect the plugs of lamps when the relays are 
switched off by the "maintenance mode", otherwise 
the relays may be damaged (see section 5.8). 
The relays of the Ballast Connect Micro are not 
covered by warranty. 

 

2. Operation 

 
The Ballast Connect Micro is intended for switching 2 
lights on and off. The lamps are switched on and off 
one at a time, with an interval of 5 seconds. If the 
connected Temp Probe measures a temperature above 
the set "Overheat T" value, 1 relay will be turned off. 
This can be a random lamp, but there is also the option 
to always switch off relay L2. In this case L1 (lamp 1) 
remains switched on, even during an over-temperature 
situation (see section 5.5). Only when the temperature 
drops below the "Normal" value the lamp will be 
switched on again. 
 

2.1 Hybrid relays 

 
The Ballast Connect Micro can switch 2 x 600W 
(maximum 1200W). Each lamp is switched individually 
by means of hybrid relays, to avoid peak flows. 
 

2.2 Temperature protection 

 
The Ballast Connect Micro has temperature protection. 
In case of an over-temperature situation, 1 lamp will be 
turned off until the desired temperature is reached 
again. This can be a random lamp, but there is also the 
option to always switch off relay L2. In this case L1 
(lamp 1) remains switched on, even during an over-
temperature situation (see section 5.5). 
 

This function only works if a Temp Probe is connected 
(not supplied). 

 
ATTENTION: Before connecting the Temp Probe you 
must first switch off the Ballast Connect Micro via 
the "maintenance mode" (see section 5.8). Then 
disconnect the Ballast Connect Micro from the 
socket. Plug the Temp Probe into the Ballast 
Connect Micro and reconnect the Ballast Connect 
Micro to the socket. 
 

2.3 Asymmetric time clock 

 
The Ballast Connect Micro has 2 different time clocks: a 
24-hour timer and an asymmetric timer. The 
asymmetric timer allows you to extend or shorten the 
24-hour cycle. 
 

2.4 Switch-on delay 

 
In the event of a power failure, the controller can delay 
switch-on. You can select delay times up to 300 
minutes. 
 

3. Which sensors can be connected to 
the Ballast Connect Micro? 

 
Only a Temp Probe can be connected to the Ballast 
Connect Micro. The Temp Probe is available in lengths 
of 2 meter, 5 meter and 10 meter.  
The Ballast Connect Micro can not monitor temperature 
if there is no connection with a Temp Probe. In this 
case, temperature protection does not work! 
 

ATTENTION: Before connecting the Temp Probe you 
must first switch off the Ballast Connect Micro via 
the "maintenance mode" (see section 5.8). Then 
disconnect the Ballast Connect Micro from the 
socket. Plug the Temp Probe into the Ballast 
Connect Micro and reconnect the Ballast Connect 
Micro to the socket. 

 

4. Meaning LEDs 

 
L1-L2:  indicates that the relay is switched on. 
 

In the event of a malfunction, the LED will 
be off and the outlet will be on. In that case, 
contact the seller of the Ballast Connect 
Micro. 

 

Содержание Ballast Basic Micro

Страница 1: ...TechGrow Innovative Growing Solutions Ballast Connect Micro Handleiding User Manual Manuel Manual Manuell www techgrow nl...

Страница 2: ...______________________________________ 9 5 3 Instellen timer_____________________________________________________________________________________________10 5 4 Instellen opstartvertraging_____________...

Страница 3: ...________________________________20 2 Fonctionnement_______________________________________________________________________________________________20 2 1 Relais hybrides _______________________________...

Страница 4: ...__________________29 5 7 Temperatura m nima m xima mostrada _______________________________________________________________29 5 8 Apagando los rel s MANUALMENTE _______________________________________...

Страница 5: ..._________________________________________________________________________35 5 7 Anzeige der Minimal Maximaltemperatur ____________________________________________________________35 5 8 Die Relais auss...

Страница 6: ...n lamp in de Ballast Connect Micro en verwijder NOOIT een stekker van een lamp uit de Ballast Connect Micro als de relais stopcontacten aanstaan U mag uitsluitend stekkers van lampen aansluiten of ver...

Страница 7: ...____________________________________ TechGrow Innovative Growing Solutions 7 Technische specificaties Stroomverzorging 100 tot 240 V Netfrequentie 50 tot 60 Hz Opname 3 W Zekering 1 x 10 A Schakelverm...

Страница 8: ...stromen tot het verleden 2 2 Temperatuurbeveiliging De Ballast Connect Micro beschikt over temperatuurbeveiliging Bij een overtempsituatie zal n lamp worden uitgeschakeld tot de gewenste temperatuur w...

Страница 9: ...u komt dan ook in het hoofdmenu Plaats de cursor bij Set clock en druk op de DDK Hier kunt u de datum en tijd instellen door aan de DDK te draaien Door op de DDK te drukken gaat u naar de volgende wa...

Страница 10: ...de Temp Probe dient u de Ballast Connect Micro eerst uit te schakelen via de maintenance mode zie paragraaf 5 8 Daarna haalt u de spanning van de Ballast Connect Micro Sluit de Temp Probe aan en steek...

Страница 11: ...IG Als u tussentijds de relais wilt uitschakelen omdat u een stekker wilt verwisselen doorloopt u de volgende stappen U bent nu in het hoofdmenu Selecteer maintenance Druk op de DDK U ziet nu het volg...

Страница 12: ...lamp into the Ballast Connect Micro and NEVER remove a lamp s plug from the Ballast Connect Micro when the relays sockets are on You may only connect or disconnect the plug s of the lamp s when the r...

Страница 13: ..._________________________________________ TechGrow Innovative Growing Solutions 13 Technical specifications Power supply 100 to 240V Mains frequency 50 to 60 Hz Own Consumption 3W Fuse 1 x 10A Switchi...

Страница 14: ...s temperature protection In case of an over temperature situation 1 lamp will be turned off until the desired temperature is reached again This can be a random lamp but there is also the option to alw...

Страница 15: ...next step Confirm the setttings by selecting Ok and pressing the PTK or select Ca to cancel Select HOME to access the main screen 5 2 Clock Timer selection You are in the main menu Select Timer mode...

Страница 16: ...robe into the Ballast Connect Micro and reconnect the Ballast Connect Micro to the socket You are in the main menu Select Temperature Set the values for normal en overheat Press the PTK to return to t...

Страница 17: ...all relays because you want to change plugs go through the following steps You are in the main menu Select maintenance Press the PTK to access the next screen The LEDs of L1 and L2 now go off one by o...

Страница 18: ...cro et ne retirez JAMAIS la fiche de la lampe du Ballast Connect Micro Vous pouvez connecter ou d connecter la les prise s du des lampe s lorsque les p riodes sont d sactiv es par le mode maintenance...

Страница 19: ..._____________________________ TechGrow Innovative Growing Solutions 19 Sp cifications techniques Alimentation 100 240V Fr quence r seau 50 60 Hz Propre consommation 3W Fusible 1 x 10A Capacit de commu...

Страница 20: ...e la temp rature Le Ballast Connect Micro est dot d une protection contre la temp rature En cas de surchauffe 1 lampe sera teinte jusqu ce que la temp rature d sir e soit nouveau atteinte Cela peut tr...

Страница 21: ...ock et appuyez sur le PTK Tournez le PTK pour ajuster la date et l heure en appuyant entre les touches PTK pour passer l tape suivante Confirmez les param tres en s lectionnant Ok et en appuyant sur l...

Страница 22: ...une sonde de temp rature non fournie soit connect e au Ballast Connect Micro ATTENTION Avant de connecter la temp rature Vous devez d abord teindre le Ballast Connect Micro via le mode maintenance voi...

Страница 23: ...ctiver les relais MANUELLEMENT Si vous souhaitez d sactiver tous les relais car vous souhaitez modifier les prises proc dez comme suit Vous tes dans le menu principal S lectionnez maintenance Appuyez...

Страница 24: ...mpara del Ballast Connect Micro cuando los rel s ranuras est n prendidos Usted s lo puede conectar o desconectar el enchufe s de la l mpara s cuando los rel s son cambiados por el modo de mantenimien...

Страница 25: ...________________________________ TechGrow Innovative Growing Solutions 25 Especificaciones T cnicas Fuente de poder 100 a 240V Frecuencia principal 50 a 60 Hz Consumo propio 3W Fusible 1 x 10 Capacida...

Страница 26: ...la temperatura El Ballast Connect Micro tiene una protecci n de temperatura En caso de una situaci n de un sobrecalentamiento 1 l mpara ser apagada hasta la temperatura deseada se consiga de nuevo Est...

Страница 27: ...undos para acceder el men principal Ponga el cursor del frente en Set clock y presione el PTK Gire el PTK para ajustar la fecha y hora mientras hace esto presione el PTK para ir al siguiente paso Conf...

Страница 28: ...a al Ballast Connect Micro ATENCI N Antes de conectar la sonda de temperatura primero debe apagar el Ballast Connect Micro a trav s del modo de mantenimiento vea secci n 5 8 Luego desconecte el Ballas...

Страница 29: ...ENTE Si quiere apagar los rel s porque quiere cambiar los enchufes siga estos pasos Usted debe estar en el men principal Seleccione maintenance Presione el PTK para acceder a la siguiente pantalla El...

Страница 30: ...en Sie NIEMALS den Stecker einer Lampe aus dem Ballast Connect Micro wenn die Relais Buchsen eingeschaltet sind Sie d rfen den die Stecker der Lampe n nur dann anschlie en oder entfernen wenn die Rela...

Страница 31: ..._____________________________________________ TechGrow Innovative Growing Solutions 31 Technische Daten Stromversorgung 100 bis 240V Netzfrequenz 50 bis 60 Hz Eigenverbrauch 3W Sicherung 1 x 10A Schal...

Страница 32: ...tr me zu vermeiden 2 2 Temperaturschutz Das Ballast Connect Micro ist temperaturgesch tzt Im Falle einer bertemperatur wird 1 Lampe ausgeschaltet bis die gew nschte Temperatur wieder erreicht ist Dies...

Страница 33: ...das Hauptmen angezeigt Wenn Sie sich im Hauptbildschirm befinden dr cken Sie die PTK Taste 5 Sekunden lang um in das Hauptmen zu gelangen Stellen Sie den Cursor auf Uhr stellen Set clock und dr cken S...

Страница 34: ...en um zum Hauptbildschirm zur ckzukehren 5 5 Temperatureinstellungen Am Ballast Connect Micro k nnen Sie die Temperatur Normal und berhitzung einstellen vorausgesetzt dass ein Temperaturf hler nicht m...

Страница 35: ...werte werden angezeigt Dr cken Sie die PTK Taste 3 Sekunden lang um Mn Mx zur ckzusetzen 5 8 Die Relais ausschalten MANUELL Wenn Sie alle Relais ausschalten m chten weil Sie den Stecker wechseln wolle...

Отзывы: