VEGA KS ( 1/2/3) KVA MANUAL
8
Figure1Securing the Rails
b)
Select the proper size in the rack for positioning the UPS (see Figure 2). The
railoccupies four positions on the front and rear of the rack.
c)
Tighten four M5 Umbrella Nuts in the side of rail assembly(see Figure 1).
d)
Fix one rail assembly to the front of the rack with one M5×12 pan-head screw
and one M5 cage nut. Using two M5 cage nuts and two M5×12 pan-head
screws, to fix the rail assembly to the rear of the rack.
Figure2Fixing the Rails
e)
Repeat Steps 3 and 4 for the other rail assembly.
f)
Tighten the four butterfly nuts in the middle of each rail assembly.
g)
If installing optional cabinets, repeat Step 1 through Step 6 for each rail kit.
h)
Place the UPS on a flat, stable surface with the front of the cabinet facing to
you.
i)
Align the mounting brackets with the screw holes on each side of the UPS and
fix with the supplied M4×8 flat-head screws(see Figure 3)
Figure3Installing the Mounting Brackets