20
10.3.2 LTL models
To fix the limit switch on the level gauge, loosen the nuts (D), move the switch to the desired
height and tighten the nuts (D) again.
The position of the reading point of the float with respect to the switching point of the limit
switch can vary from one type of float to another. If it is the first time that the switching point
is adjusted, with the float in a stable position, move the limit switch until the inductive sensor
switches.
10.4 Electrical
connection
For the electrical installation it is recommended to use multiple conductor cables, and not
single cables, in order to guarantee the cable gland will stay watertight. The connector has a
PG9 cable gland for cables with outer diameters between 5 mm and 7 mm. The numbering
of the terminals is the following:
In the female connector (A):
Terminal 1:
Negative (Blue sensor cable)
Terminal 2:
Positive (Brown sensor cable)
Terminal 3:
Not connected
Earth terminal: Earth
D
Содержание LT106
Страница 1: ...R MI LT Rev 3 english version Instructions manual The art of measuring Series LT Level gauge...
Страница 41: ...41 LT LTL15 PTFE All dimensions in mm LT LTL14 PP PVC PVC C PVDF According to DN According to DN...
Страница 42: ...42 All dimensions in mm LTL APR LT APR LT AMM AMD LTL AMM AMD...
Страница 43: ...43 LT AAR All dimensions in mm LT xxx ADF LTL xxx ADF...
Страница 44: ...44 22 ATEX CERTIFICATE...
Страница 45: ...45...
Страница 46: ...46 23 ATEX DECLARATION OF CONFORMITY...
Страница 47: ...47...