Appendix A 

    Quick Guides for Using the DG-700 with Energy Conservatory Test Devices  

 

 

Fan Configuration 

Flow Range (cfm) 

For Series B Duct Blaster

 

Open (no Flow Ring) 

1,500 - 600 

Ring 1 

              800 – 225 

Ring 2 

              300 – 90 

Ring 3 

              125 – 10  

 

 

A.2   One-Point 25 Pascal Total Leakage Duct Pressurization Test Using the Series B Minneapolis 
Duct Blaster

 and DG-700 Digital Gauge 

  

 

1.

 

Connect the Duct Blaster fan to the duct system. 
a)

 

Choose a location to install the Duct Blaster fan. In single, double or triple returned systems, the largest and 

closest return to the air handler is usually the best choice. Note: In multi-return systems (a return in every room), 
installing at the air handler cabinet is often best.   

b)

 

Remove any remote filters from the chosen return and then connect the black square transition piece to the return 

using temporary tape. Completely seal the remaining open area of the return with tape.   

c)

 

Pull the Duct Blaster fan and flex duct out of the carrying case. Connect the flex duct to the 

exhaust

 side of the 

fan (i.e. the side with the metal guard) using the round transition piece and connect trim. Connect the open end of the 
flex duct to the square transition piece using the velcro strap on 
the flex duct. 

d)

 

Connect the fan speed controller to the fan and plug it into a 

grounded power outlet.   

e)

 

Install the Flow Ring which you think best matches the 

needed fan flow. 

f)

 

If your DG-700 gauge and fan speed controller are 

compatible with Cruise Control, install the fan control cable into the 3.5 mm communication jacks located on top of 
the DG-700 and on the side of the speed controller (otherwise skip this step).  

 

2.

 

Prepare the duct system and house for the Test. 
a)

 

Adjust the HVAC system controls so that the air handler does not turn on during the Test.  

b)

 

Temporarily seal off all remaining supply and return registers, and combustion or ventilation air inlets which are 

connected to the duct system. Use 

Duct Mask

 temporary register sealing material provided with your Duct Blaster, 

or use painters tape and paper. 

c)

 

Turn off any exhaust fans, vented dryers, and room air conditioners. 

d)

 

Remove all central filters (i.e. in air handler or return plenum). 

e)

 

Open a door or window between the house and outside to prevent changes in house pressure when the Duct 

Blaster is running. 

f)

 

If the Duct Blaster is installed in an attic, garage or crawlspace - open vents or access panels or doors from these 

spaces to the outside. 

 

3.

 

Connect tubing to DG-700 Pressure Gauge.  
a)

 

Select a location to measure duct 

pressure. The best location for measuring duct 
pressure is often in the supply trunkline or 
plenum. Drill a small hole (1/4" to 3/8" OD) 
into the duct to allow a static pressure probe to 
be installed. Install the static pressure probe 
with the end of the probe pointing into the air 
flow from the Duct Blaster fan. If the duct 
system is reasonably airtight (e.g. less than 
200 cfm25 of leakage), duct pressures can be 
measured at any supply register by inserting 
the end of the tubing through the temporary 
register seal.   

b)

 

Connect tubing to the DG-700 as shown 

in the illustration to the right.  

 

4.

 

Conducting the Test. 
a)

 

Turn on the gauge by pressing the 

ON/OFF

 button.  

b)

 

Press the 

MODE

 button three times to put the guage into the 

PR/ FL @25 

Mode. In this Mode, 

Channel A

 is 

used to measure duct system pressure while 

Channel B

 is used to display estimated duct leakage at a test pressure of 

25 Pascals. (The leakage estimate shown on 

Channel B

 is determined by mathematically adjusting the actual air flow 

from the Duct Blaster fan using the 

Channel A

 duct system pressure reading and a Can’t Reach Pressure factor.) 

Connect to space where 
fan is installed (if fan and 
gauge are in the same 
space, leave open). 

To Duct Blaster Fan 
(brass tap in middle 
of fan housing) 

Connect to inside of house (if 
gauge is installed in the house, 
leave this tap open). Be sure 
window is open. 

To Duct System  
(insert into register  
or connect to static 
pressure probe) 

 

28 

Operating Instructions 

for the DG700

 

Содержание DG-700

Страница 1: ...Operating Instructions for the DG 700 Pressure and Flow Gauge...

Страница 2: ......

Страница 3: ...Operating Instructions for the DG 700 Pressure and Flow Gauge The Energy Conservatory 2801 21st Ave S Suite 160 Minneapolis MN 55407 Ph 612 827 1117 Fax 612 827 1051 www energyconservatory com...

Страница 4: ...f all other warranties and is subject to the conditions and limitations stated herein NO OTHER EXPRESS OR IMPLIED WARRANTY IS PROVIDED AND THE SELLER DISCLAIMS ANY IMPLIED WARRANTY OF FITNESS FOR PART...

Страница 5: ...ime Averaging Measurement Buffer 5 1 6 Overview of the Baseline Pressure Measurement Feature Channel A 6 1 6 a Buttons Used with Baseline Pressure Feature 6 1 6 b Restarting the Baseline Measurement 7...

Страница 6: ...Pressure Air Handler Flow Mode 19 5 3 Changing the Selected Test Device and Configuration 19 5 4 or LO Displayed on Channel B 20 5 5 Changing the Air Handler Flow Units 20 5 6 Changing the Time Averag...

Страница 7: ...del 3 Minneapolis Blower Door and DG 700 Digital Gauge 26 A 2 One Point 25 Pascal Total Leakage Duct Pressurization Test Using the Seried B Minneapolis Duct Blaster and DG 700 Digital Gauge 28 A 3 Usi...

Страница 8: ...er to measure and record a baseline pressure reading and then display the baseline adjusted pressure reading 1 1 b Auto Zeroing Auto zeroing feature for both measurement channels automatically adjusts...

Страница 9: ...ure Flow PR FL Multi purpose pressure and air flow measurements Pressure in Pascals Nominal unadjusted air flow from the selected Energy Conservatory test device in units chosen CFM m3 h l s Pressure...

Страница 10: ...Used to exit out of a Baseline pressure measurement procedure When in PR AH mode resets gauge back to beginning of AH flow measurement procedure i e NSOP measurement Also used to turn off the Cruise C...

Страница 11: ...onnect the DG 700 to a user supplied laptop computer 1 4 b Fan Control Output Jack The fan control output jack provides a speed control signal which is used to control a Blower Door or Duct Blaster fa...

Страница 12: ...reading is fluctuating more than desired Long Term Average L Both measurement channels are updated once per second with the running average of all readings taken after the Long Term Average period is...

Страница 13: ...le below the building depressurization measured from the exhaust fan operating is 4 2 Pascals i e the building pressure changed from 2 6 Pa to 6 8 Pa when the exhaust fan was turned on 1 6 a Buttons U...

Страница 14: ...ressure the baseline measurement procedure can be restarted by pressing the START button When START is pressed the measurement buffer and time counter for the baseline reading is cleared and a new bas...

Страница 15: ...to For example let s set up the gauge to measure the pressure in a house with reference to outside using Channel A If you are standing in the house connect tubing to the Channel A Reference tap and r...

Страница 16: ...ing pressure caused by fan operation Set up Channel A to measure building pressure with reference to outside e g run tubing from the Channel A Reference tap to outside and leave the Channel A Input ta...

Страница 17: ...depressurization measured from the exhaust fan operating is 4 2 Pascals i e the building pressure changed from 2 6 Pa to 6 8 Pa when the exhaust fan was turned on While displaying the baseline adjust...

Страница 18: ...units on Channel B is CFM cubic feet per minute and the default selected test device is the Model 3 110V Minneapolis Blower Door The default time averaging period is 1 second average 3 3 Changing the...

Страница 19: ...3 7 Using the Baseline Pressure Feature in Pressure Flow Mode The Baseline feature on Channel A allows the user to measure and record a baseline pressure reading and then display the baseline adjusted...

Страница 20: ...rts back to whatever period was selected prior to pressing the BASELINE button Channel B is now set up to display the air flow through the Blower Door fan it will read LO until the fan is turned on No...

Страница 21: ...ssure of 50 Pascals The leakage estimate shown on Channel B is determined by mathematically adjusting the measured air flow from the selected Blower Door fan using the real time Channel A building pre...

Страница 22: ...inneapolis Blower Door fans BD 3 Model 3 220V Minneapolis Blower Door fans BD 3 220 Model 4 220V Minneapolis Blower Door fans BD 4 Series A Minneapolis Duct Blaster fans DB A Series B Minneapolis Duct...

Страница 23: ...s commonly used during both building and duct airtightness test procedures where the user wishes to display the actual change in building or duct pressure caused by operation of the Blower Door or duc...

Страница 24: ...in the 25 mode square inches The following equation is used to estimate leakage area when in the 25 mode square centimeters 4 8 c Errors in Leakage Estimates Tables 4 1 and 4 2 below show the errors i...

Страница 25: ...0 0 0 0 55 1 4 1 0 0 5 0 0 0 5 0 9 60 2 8 1 8 0 9 0 0 0 9 1 8 65 4 0 2 7 1 3 0 0 1 3 2 6 Actual exponent n Table 4 1 Error in Leakage Estimate for 50 Mode 0 5 0 55 0 6 0 65 0 7 0 75 Test 5 14 9 7 7 0...

Страница 26: ...e NSOP pressure measurement and pressing ENTER records and enters the NSOP reading into the gauge Step 2 Once the NSOP measurement is made and entered into the gauge Step 1 the gauge is set up to simu...

Страница 27: ...n units of CFM m3 hr and l s The default air flow unit is CFM To change the flow units for Channel B press the UNITS button while in the Step 2 part of the procedure The selected flow units are shown...

Страница 28: ...ly the more stable the reading typically becomes In the screen to the right the measured NSOP pressure is 56 7 Pascals measured over the past 30 seconds Once you are satisfied with the NSOP reading pr...

Страница 29: ...fluctuating change the time averaging setting to 5 second 10 second or long term average using the TIME AVG button Note If you are unable to get the TFSOP to within 5 Pascals of the NSOP reading the g...

Страница 30: ...ing mode the DG 700 can display air velocity readings on Channel B in units of feet per minute or meters per second To change the air velocity units for Channel B press the UNITS button The selected u...

Страница 31: ...powered by 6 AA batteries located in the battery compartment on the back of the gauge We recommend that Alkaline or rechargeable batteries e g nickel metal hydride or NiCd be used with this gauge When...

Страница 32: ...olarity as illustrated on the inside of the battery compartment Turn the gauge back on If neither of the steps above takes care of the problem you will need to send the gauge back to The Energy Conser...

Страница 33: ...to blow air out of the building h The remaining end of the Red tubing should now be connected to the pressure tap on the Blower Door fan electrical box i If your DG 700 gauge and fan speed control are...

Страница 34: ...ise As the fan speed increases the building depressurization displayed on Channel A should also increase Continue to increase the fan speed until the building depressurization shown on Channel A is be...

Страница 35: ...the duct system Use Duct Mask temporary register sealing material provided with your Duct Blaster or use painters tape and paper c Turn off any exhaust fans vented dryers and room air conditioners d R...

Страница 36: ...justing the fan speed control to achieve a test pressure of exactly 25 Pascals e Channel B will now display the One Point 25 Pascal Total Duct Leakage estimate If the leakage estimate is fluctuating m...

Страница 37: ...erence tap on Channel A open If the gauge is not in the house during the test procedure e g attic crawlspace run additional tubing from the Channel A Reference tap to inside the house d Turn on the ai...

Страница 38: ...tering Plate to the DG 700 a Connect the tubing from the installed metering plate to the DG 700 Connect the Red total pressure grid tubing connection to the Channel B Input pressure tap Connect the Gr...

Страница 39: ...ed in the Blower Door operation manual 3 Connect the DG 700 to your computer using either a USB cable or a 9 pin serial communication cable If using a USB cable follow these instructions Insert the in...

Страница 40: ...lick on Device Manager From the Device Manager window open the Ports icon to show which communication ports are currently installed on your computer In the case illustrated below the computer has 3 in...

Страница 41: ...Door operation manual 6 Now turn on the Blower Door fan speed controller to the just on position the fan should not be turning in this position The speed control knob should be turned all the way dow...

Страница 42: ...th Energy Conservatory Test Devices Communication Cable USB or 9 pin Serial To Computer Fan Control Cable To Power Source Building Pressure Green Hose A Reference Fan Pressure Red Hose B Input Fan Pow...

Страница 43: ...700 will maintain a contant 25 Pa building pressure while the DG 700 gauge connected to the Duct Blaster fan maintains a constant 0 Pa pressure in the duct system Maintaining a constant building press...

Страница 44: ...sure on Channel A The fan will slowly start increasing speed until the pressure reading on Channel A matches the Cruise target pressure The fan will simply run at full speed if the target pressure can...

Отзывы: