Water flow detection 

The  heat  pump  only  operates  whenever  there is  water flow  circulating  inside.  All models  are  equipped  with  a  water 

flow switch that detects if the water pump is working or not. 

 

flow” LED lighting = water pump working.

 

 

“flow” LED not lighting = water pump stopped.

 

Internal parameters 

Button 

 serves to check the internal parameters. These parameters may only be modified by professionals. 

When the machine is displaying internal parameters, the icon 

 will be shown. 

Controller state table 

Screen 

Explanation 

Check 

Solution (if no reset) 

St-by 

Stand-by 

FLO 

No  water  flow  or  the  flow  switch 

doesn’t detect the water flow 

-  Check  if  filtration  pump  is 
working. 

 

- Check by-pass setting. 

 

- Check water flow switch position. 

Contact your seller 

AL10 / AL11 

HP error 

AL15 / AL16 

Too  much  temperature  difference 
between water in and water out. 

AL18 

Comp. Out temp. Too high 

AL17 

Low  temp  protection  in  cooling 
mode 

AL7 / AL8 

Communication error 

Check 

electrical 

connection 

between  controller  and  electronic 
card inside the machine. 

AL3 

Probe error (Water in) 

Check probe connection. 

AL4 

Probe error (Water out) 

AL5 

Probe error (coil.) 

AL1 

Probe error (comp. out) 

AL2 

Probe error (comp. in) 

AL6 

Probe error (ambiance) 

AL9 

Fan error 

Check fan connection. 

AL14 

Outdoor temperature too low 

Outdoor temp is below -15°C 

Wait 

for 

the 

outdoor 

temperature to increase. 

AL19 / AL20 

Power supply problem 

Ask  an  electrician  specialist  to 
check power supply. 

Contact your seller 

AL21  /  AL22  /  AL23 / 
AL24 / AL25 

Electronic/overheating protection 

Stop the  power  supply for  5 to  10 
minutes,  check that  air flow is  not 
blocked, turn ON power supply 

EN

 

Содержание INVERTER S

Страница 1: ...Handbook Tebas Inverter 20 1 Angielska docx Inverter...

Страница 2: ...on 5 Installation conditions 5 Hydraulic connections 6 Electrical connections 6 Heating priority 7 Utilization 8 Water connection 8 Regulation digital controller 9 Water flow setting 12 Winter setting...

Страница 3: ...hours The heat pump referred to in this handbook is designed and built solely for private swimming pool use Tebas dissociates its responsibility if used in any other application This handbook is cons...

Страница 4: ...th automatic start up fan Cutting edges evaporator In order to avoid accidents prevent close access the appliance by children and pets Never cover the appliance whilst in operation and never put your...

Страница 5: ...t side of the fan on a completely free space Make sure that the discharged air will not be sucked back into the evaporator again Provide enough space to allow access to temperature controller To impro...

Страница 6: ...on the floor or the walls so the heat pump will not support the weight of the water inside the plumbing Do not use a clamp or other tool to screw the connections hand screwing is sufficient Electrica...

Страница 7: ...y water gas they must be separated by a distance of at least 20 cm 8 Heat pump power supply must be protected by a system in conformity with local laws Heating priority It is possible to connect the w...

Страница 8: ...emperature is between 15 and 30 C 50 F and 86 F You can then start up your machine Follow the instructions below in the given order each time you start up the pool heat pump especially at the beginnin...

Страница 9: ...the machine manage its power and keep low noise low speed Heats the water up to the desired value 1 C Smart Heating mode machine manage it s power for best efficiency Heats the water up to the desire...

Страница 10: ...Adjust the desired value with or and wait a few seconds till it is stored automatically Working information 3 symbols at the left bottom corner indicate the working information First symbol indicate...

Страница 11: ...ater flow switch position Contact your seller AL10 AL11 HP error AL15 AL16 Too much temperature difference between water in and water out AL18 Comp Out temp Too high AL17 Low temp protection in coolin...

Страница 12: ...2 C by pass setting is correct between 10 and 15 C Abnormal pressure If the pressure is too high or too low it indicates that the water flow circulating inside the heat pump is not correct You need to...

Страница 13: ...nds on the exposure of swimming pool to wind sun and the pool environment as well as the heat pump size Maintaining the temperature Once the set temperature is reached you may reduce the filtration pe...

Страница 14: ...rmation together with the dimensions of the swimming pool your personal details address telephone number and the description of the failure If this procedure is respected the Tebas technician will be...

Отзывы: