- 5 - 

 

TDK-Lambda 

ZWS10

15B

30B Series 

Instruction Manual

 

4-3. Inrush Current 

This series equipped Power thermistor to limit the inrush current. Higher inrush current will flow at higher ambient temperature or re-input 
condition. Please select input switch and fuse carefully with the high temperature and re-input the power condition. The Inrush Current value 
is under cold start at 25

  in the specification. 

 

4-4. Over Voltage Protection (OVP) 

The OVP function (Inverter shut down method, manual reset type) is provided. Please refer to its specification for OVP operating range. 
When OVP trigger, the output will be shut down. To reset OVP, remove the input of power supply for a few minutes, and then re-input. In 
addition, the setting value of OVP is fixed and not adjustable. Pay attention not to apply higher voltage externally to the output terminal to 
avoid unit failure. In case of inductive load, put protective diode in series to the output power line. 

 

4-5. Over Current Protection (OCP) 

ZWS10B, ZWS15B, ZWS30B: Hiccup mode with automatic recovery. 
OCP function operates when the output current exceeds 105% of maximum DC output current of specification. The outputs will be 
automatically recovered when the overload condition is canceled. Never operate the unit under over current or shorted conditions for more 
than 30seconds, which may leads damage or insulation failure. OCP setting is fixed and not to be adjusted externally.   

 

4-6. Output Ripple & Noise 

The standard specification for maximum ripple value is measured according to measurement circuit specified by JEITA-RC9131B. When 

load lines are longer, ripple will becomes larger. In this case, electrolytic capacitor, film capacitor, etc. might be necessary to use across the 
load terminal. The output ripple cannot be measured accurately if the probe ground lead of oscilloscope is too long. For start up at low 
ambient temperature and low input voltage, output ripple noise might not meet specification. However, output ripple noise specification can 
be met after one second.   

 
 
A circuit reducing light load input power consumption is built in ZWS10B, ZWS15B, ZWS30B (Input power : 0.2W typ, 0.5W max at no 

load).  When  output  current  is  within  0-35%  of  rated  load,  the  internal  switch  element  is  intermittent  operated, and  the  switching  loss  is 
decreased. The specification of the Ripple & Noise changes by this intermittent operation. The dynamic load response characteristic changes 
by  this  intermittent  operation too.  Different  input  voltage  and  dynamic  load  condition  has  different  dynamic  load response characteristic. 
Please contact us for details.   

 

Load

C1

150mm

C2

Coaxial Cable

1.5m 50

Ω

R1

C3

Oscilloscope
Bandwidth : 100MHz

Power

Supply

+

C1 : 0.1uF     Film Cap. 
C2 : 100uF    Electric Cap. 
C3 : 4700uF  Ceramic Cap. 
R1 : 50

Ω

A

 

 

4-7. Series Operation   

For series operation, either method (A) or (B) is possible. 

 

 

(*1)Please select a bypass diode with maximum forward current rating more than output load current. And maximum reverse voltage must 

withstand each power supply output voltage.   

 
 

Output 
Terminal 

(A) 
Power Supply 

Output 
Terminal 

Load

 

Output 
Terminal 

(B) 
Power Supply 

Output 
Terminal 

Load 

Load 

(*1) 

C3 : 4700pF    Ceramic Cap.   

Содержание ZWS-B Series

Страница 1: ...responsible after the product has been modified changed or dis assembled 6 Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc Please stop using i...

Страница 2: ...her the frame ground terminal of the product and the ground terminal of the equipment for safety and noise reduction If these ground is not connected together there is risk of electric shock 13 Parts...

Страница 3: ...put terminal Live line Fuseinline N AC Input terminal Neutralline Earth Terminal Mounting hole hole diameter 3 5mm This hole is connectedto terminal of CN1 Must beconnectedtoelectricallyconductivespac...

Страница 4: ...R 5N SVH 21T P1 1 BVH 21T P1 1 J S T Output CN51 ZWS10B ZWS15B B2P VH LF SN VHR 2N Output CN51 ZWS30B B4P VH LF SN VHR 4N Hand CrimpingTool YC 160R J S T 4 Explanation of Function and Precautions 4 1...

Страница 5: ...fication for maximum ripple value is measured according to measurement circuit specified by JEITA RC9131B When load lines are longer ripple will becomes larger In this case electrolytic capacitor film...

Страница 6: ...done before the test Ensure that the unit is fully discharged after the test Output 500VDC More than 100M AC L AC N Isolation Tester 4 10 Withstand Voltage This series is designed to withstand 3 0kVA...

Страница 7: ...g below Load of derating curve indicates output power 5 2 Output Derating vs Ambient temperature Make sure that the specified temperature range is maintained Operate the unit out of the specified dera...

Страница 8: ...e of PCB air must flow through component side As a reference for forced air cooling let air flow so that the C51 temperature is lower than Electrolytic capacitor allowable max temperature in the below...

Страница 9: ...ies Instruction Manual ZWS30B ZWS10B ZWS15B C51 C51 C51 CN1 CN1 CN1 INPUT INPUT INPUT 5 3 Output Derating vs Input Voltage Output derating is required when the power supply operate below 90VAC input R...

Страница 10: ...8 8 8 8 8 8 Condition to meet Isolation Withstand Voltage standard More than 4mm More than 4mm More than 4mm More than 4mm More than 4mm More than 8mm Keep 4mm space from the surfaces and sides of PC...

Страница 11: ...o input current RMS values under the actual load condition ZWS10B ZWS15B 2 0A ZWS30B 3 15A 8 Before concluding that the unit is at fault 1 Check if the rated input voltage is connected 2 Check if the...

Страница 12: ...inquire our company ZWS10B ZWS30B CONVECTION COOLING ZWS15B CONVECTION COOLING ZWS10B ZWS15B ZWS30B FORCED AIR COOLING Following cases are not covered by warranty 1 Improper usage likedroppingproduct...

Отзывы: