TDK-Lambda 

ZWS10

15B

30B Series 

Instruction Manual

 

 

3. Terminal Connection Method 

 

 

Pay attention to the input wiring. If it is connected to wrong terminal, the power supply will be damaged. 

 

Input must be off when making connections. 

 

Connect terminal of input connector and mounting hole to protective earth of the equipment. 

 

The output load line and input line shall be separated to improve noise sensitivity. 

 

Do not apply stress to PCB, when connecting or removing connector. 

 

Do not apply stress to other components (especially VR51 and C51), when connecting or removing connector. 

 

Use input/output connector (housing) specified by the table below. 

 

Use recommended crimping tool. Connector is not included with this product. (Refer to the following)

 

 

 

   
 

Input/Output Connector 

 

 

Model 

Connector 

Housing 

Terminal Pin 

Maker 

Input ( CN1 ) 

Common 

B3P5-VH(LF)(SN) 

VHR-5N 

SVH-21T-P1.1 

BVH-21T-P1.1 

J.S.T. 

Output ( CN51 ) 

ZWS10B, ZWS15B 

B

2

P-VH(LF)(SN) 

VHR-2N 

Output ( CN51 ) 

ZWS30B 

B

4

P-VH(LF)(SN) 

VHR-4N 

Hand Crimping Tool : YC-160R

 

(J.S.T.) 

 

 

4

Explanation of Function and Precautions 

4-1. Input Voltage Range 

Input voltage range is single phase 85-265VAC (47-63Hz). Never operate the unit out of the specified input voltage range to avoid unit 
failure. 
For cases where conformance to various safeties required, input voltage range will be 100-240VAC (50/60Hz).   
 

4-2. Output Voltage Range 

Output voltage is set the rated value at shipment. V.ADJ trimmer (VR51) can adjust the output voltage within the range. Output voltage range 
is within 

±

10% of nominal output voltage. To turn the trimmer clockwise, the output voltage will be increased. Take note when the output 

voltage is increased excessively, over voltage protection (OVP) function may trigger and voltage will be shut down. Furthermore, when 
increasing the output voltage reduce the output current so as not to exceed the maximum output power. 

 

Содержание ZWS-B Series

Страница 1: ...responsible after the product has been modified changed or dis assembled 6 Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc Please stop using i...

Страница 2: ...her the frame ground terminal of the product and the ground terminal of the equipment for safety and noise reduction If these ground is not connected together there is risk of electric shock 13 Parts...

Страница 3: ...put terminal Live line Fuseinline N AC Input terminal Neutralline Earth Terminal Mounting hole hole diameter 3 5mm This hole is connectedto terminal of CN1 Must beconnectedtoelectricallyconductivespac...

Страница 4: ...R 5N SVH 21T P1 1 BVH 21T P1 1 J S T Output CN51 ZWS10B ZWS15B B2P VH LF SN VHR 2N Output CN51 ZWS30B B4P VH LF SN VHR 4N Hand CrimpingTool YC 160R J S T 4 Explanation of Function and Precautions 4 1...

Страница 5: ...fication for maximum ripple value is measured according to measurement circuit specified by JEITA RC9131B When load lines are longer ripple will becomes larger In this case electrolytic capacitor film...

Страница 6: ...done before the test Ensure that the unit is fully discharged after the test Output 500VDC More than 100M AC L AC N Isolation Tester 4 10 Withstand Voltage This series is designed to withstand 3 0kVA...

Страница 7: ...g below Load of derating curve indicates output power 5 2 Output Derating vs Ambient temperature Make sure that the specified temperature range is maintained Operate the unit out of the specified dera...

Страница 8: ...e of PCB air must flow through component side As a reference for forced air cooling let air flow so that the C51 temperature is lower than Electrolytic capacitor allowable max temperature in the below...

Страница 9: ...ies Instruction Manual ZWS30B ZWS10B ZWS15B C51 C51 C51 CN1 CN1 CN1 INPUT INPUT INPUT 5 3 Output Derating vs Input Voltage Output derating is required when the power supply operate below 90VAC input R...

Страница 10: ...8 8 8 8 8 8 Condition to meet Isolation Withstand Voltage standard More than 4mm More than 4mm More than 4mm More than 4mm More than 4mm More than 8mm Keep 4mm space from the surfaces and sides of PC...

Страница 11: ...o input current RMS values under the actual load condition ZWS10B ZWS15B 2 0A ZWS30B 3 15A 8 Before concluding that the unit is at fault 1 Check if the rated input voltage is connected 2 Check if the...

Страница 12: ...inquire our company ZWS10B ZWS30B CONVECTION COOLING ZWS15B CONVECTION COOLING ZWS10B ZWS15B ZWS30B FORCED AIR COOLING Following cases are not covered by warranty 1 Improper usage likedroppingproduct...

Отзывы: