INSTRUCTION MANUAL
ZWP350-1000 Series
TDK-Lambda
<Page>
14/23
7. Mounting Directions
7-1. Mounting Directions
The standard mounting is direction (A). Direction (B) to (F) are also possible. Use power supply within the
output derating (output power or current versus operating ambient temperature) according to mounting
direction and actual operating ambient temperature. Refer to section 7-3 Output Derating according to the
Mounting Direction. This series can be used under convection cooling and forced air cooling. In the case of
using at forced air cooling, entire component must be cool down. An air velocity of more than 2.2m/s is
required to flow through the power supply as a guide. For details, refer to section 7-3 FORCED AIR
COOLING CONDITION.
Mounting A (Standard Mounting)
INPUT
(CN1)
OUTPUT
(CN51,CN52)
OUTPUT
(CN51,CN52)
INPUT
(CN1)
Mounting D
INPUT
(CN1)
OUTPUT
(CN51,CN52)
Mounting E
Mounting B
INPUT
(CN1)
Mounting C
INPUT
(CN1)
Mounting F
INPUT
(CN1)
OUTPUT
(CN51,CN52)