Figure3-2 Control Circuit fo Parallel Operation
3. PH300S, 600S Parallel Operation
1 INTORDUCTION
PH300S, 600S series are applicable to operate in parallel
with an external circuit using CS signal terminal.
There are 2 different kinds of parallel operation.
(1)Parallel Operation
It is possible to enhance the output when load current can
not be supplied by only one power module or to improve
the reliability by derating the output power of each module.
(2)N+1 Parallel Redundant Operation
For power supply that is required high reliability, it is pos-
sible to achieve the requirement by using N+1 units of
power modules for the load of N units.
In N+1 units of parallel operation, even through one of the
power modules is failed the performance of the system
shall be maintained because the other units cover the fail-
ure module and share the load currents.
2 PRECUATIONS
There are several basic cautions and warnings in parallel
operation of PH300S, 600S series.
● Externally attach a control circuit of parallel operation
in each power module.
● Available to use 11 units maximum of power modules in
identical model (same output power and voltage.)
● Use specified components followed by explanations of
basic connection in Instruction Manual at input and out-
put side.
● Set the accuracy of the output voltage within ±1% to
adjust the output voltage.
● Set the maximum load current below 95% of sum of the
nominal output current values.
● Use same length and size of output load lines between
power module and load in parallel connection.
3 CONNECTION CIRCUIT OF PARALLEL OPEARTION
(a)Basic Connection Circuit of Parallel Operation
Load
Control Circuit of
Parallel Operation
Control Circuit of Parallel Operation
Figure3-1 Basic Connection Circuit of Parallel Operation
Basic circuit connection is shown in Figure3-1. For control
circuit of parallel operation, individually connect a circuit
shown in Figure3-2 to each PH300S, 600S series of pow-
er module of parallel operation.