3-12. Output Peak Power
Operating conditions for peak power/current models:
(a)
Reduce peak current according to output derating curve for higher ambient temperature
(see section 5.1)
(b)
Output might shut down when the rated current or the continuous peak output time (
τ
)
exceeded rated value specified. Power supply may shut down and operate in hiccup or
constant current limiting mode.
Input voltage :
115 ~ 230 VAC +/- 20% (50/60 Hz)
Continuous peak out time (
τ
) :
< 10s
Peak output current (Ip) :
Within the rated peak output current
Duty: not more than 35%
τ
Duty = ---- x 100 (%)
T
τ
Ip
2
x ---- < Irms max
T
Applicable model for Peak Output Power :
Model Irms
max.
LS200-24 6.15
A
LS200-36 4.10
A