3-12. Output Peak Power 

Operating conditions for peak power/current models: 
(a) 

Reduce peak current according to output derating curve for higher ambient temperature 

 

(see section 5.1) 

(b) 

Output might shut down when the rated current or the continuous peak output time (

τ

)  

 

exceeded rated value specified. Power supply may shut down and operate in hiccup or   

 

constant current limiting mode. 

 

Input voltage : 

115 ~ 230 VAC +/- 20% (50/60 Hz) 

Continuous peak out time (

τ

) : 

< 10s 

Peak output current (Ip) : 

Within the rated peak output current 

 
Duty: not more than 35% 
 
             

τ 

Duty = ---- x 100 (%) 
              T   
 

 

 
 

τ 

      Ip

2

 x ----                < Irms max 

                T 

 
Applicable model for Peak Output Power : 
 

Model Irms 

max. 

LS200-24 6.15 

LS200-36 4.10 

             

 

 
 
 
 

Содержание LS 200 Series

Страница 1: ...tem equipment and notify in the system instruction manual z Never operate the unit under over current or short circuit conditions for more than 30 seconds or outside its specified Input Voltage Range...

Страница 2: ...l be weak z The protective earth PE must be connected to the instrument chassis and the chassis of this power supply unit z Remote sensing lines shall be twisted or use shielded wire z Remote ON OFF c...

Страница 3: ...ad current 2 S Remote sensing terminal for Output For remote sensing function this compensates for line drop between power supply terminals and load termi nals Connect to Vm terminal when remote sensi...

Страница 4: ...Connect CNT terminal to CNT terminal with wire Please use attached CN2 connector for each connection 2 4 Remote sensing required 1 Connect S terminal to Vm terminal of load with sensing wire 2 Connec...

Страница 5: ...ved for a few minutes and then re input for recovery of the output OVP setting is fixed and cannot be adjusted externally 3 5 Over Current Protection OCP OCP function activates when the output current...

Страница 6: ...he output 3 8 Remote ON OFF Control Remote ON OFF control is available Output can be remotely switched OFF by connecting an external logic high signal to CNT terminal versus CNT terminal And when the...

Страница 7: ...10 Series Operation For series operation either method A or B is possible Method A Method B Note In case of Method A please connect diodes to prevent the reverse voltage 3 11 Parallel Operation A B A...

Страница 8: ...down when the rated current or the continuous peak output time exceeded rated value specified Power supply may shut down and operate in hiccup or constant current limiting mode Input voltage 115 230...

Страница 9: ...500VAC between output and FG chassis each for 1 minute When testing withstands volt age set current limit of withstand voltage test equipment at 20mA Output FG chassis 100mA The applied voltage must...

Страница 10: ...ndard mounting is Method A Method B and C are also possible Refer to the Output Derating below Please do not use installation Method D E and F b Free air convection without Fan Cover Recommended stand...

Страница 11: ...10 TDK Lambda LS 200 Series INSTRUCTION MANUAL Refer to the Output Derating below Please do not use installation Method D...

Страница 12: ...exhale In the following derating curve the maximum output current please refers to PA607 01 01 LS200 3 3V 5V 7 5V 12V 15V 24V 36V 48V B LS200 L series Output Derating versus Ambient Temperature The co...

Страница 13: ...C LS200 L series for Output Derating versus Input Voltage The cooling system is convection cool or forced air exhale with airflow 3m s In the following derating curve the Y axis for maximum output cu...

Страница 14: ...have lower impedance z Noise can be reduced by connecting a film capacitor with 0 1uF capacitance across the load terminals z For safety and EMI considerations connect the FG terminal of LS200 series...

Страница 15: ...fan is operating Is fan stopped or blocked by something 7 Power supply has ventilating holes in front and the back Check if there is any blockage or dust etc 8 Is the chassis of power supply abnormall...

Страница 16: ...applies but not limited to the following 1 Average operating temperature ambient temperature of the power supply unit is under 40o C 2 Average load factor is 80 or less 3 Installation method Standard...