8.4.
Setup and Operating Instructions
CAUTION
To prevent damage to the unit, do not program the output voltage and current to
higher than the power supply rating.
8.4.1. Setting up the Power Supply for 0-5V/0-10V Isolated Programming and
Monitoring
Perform the following procedure to configure the power supply:
a) Turn the power supply AC power switch to Off.
b) Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
c) Set the Setup switch SW1, positions 1 and 2 to the UP position.
d) Set SW1, position 3 to select the Programming Voltage Range: Down=0-5V, Up=0-
10V.
e) Set SW1, position 4 to select the Monitoring Range: Down=0-5V, Up=0-10V.
f)
Ensure that SW1, positions 7 and 8 are in the Down position.
g) Connect the programming sources to the mating plug of the Isolated Programming
connector. Observe for correct polarity of the voltage source.
NOTE
J1-8 and J1-12 must be shorted together with a wire jumper.
h) Set the programming sources to the desired levels and turn the power supply ON.
8.4.2. Setting Up the Power Supply for 4-20mA Isolated Programming and Monitoring
Perform the following procedure to configure the power supply:
a) Turn the power supply AC power switch to Off.
b) Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
c) Set the Setup switch SW1, positions 1 and 2 to the Up position.
d) Set SW1, position 3 to the Up position.
e) Set SW1, position 4 to the Up position.
f)
Ensure that SW1 positions 1 and 2 are in the Up position.
g) Connect the programming source to the mating plug of the Isolated Programming
connector.
NOTE
J1-8 and J1-12 must be shorted together with a wire jumper.
h) Set the programming sources to the desired levels and turn the power supply ON.
NOTE
SW1 position 3 and 4 must be in the Up position for operation with 4-20mA