INSTRUCTION MANUAL
EZA11K Series
TDK-Lambda
<Page>
・
signals and chassis(
)
:
400VAC, 1min(100mA)
*Must connect short all pins of RS-485 and CN.
・
primary (DC320V) and secondary(DC240V)
:
2200VAC, 1min(50mA)
・
primary (DC320V) and signals
:
3000VAC, 1min(50mA)
・
secondary(DC240V) and signals
:
3000VAC, 1min(50mA)
*Must connect short all pins of RS-485 and CN.
Notes: This product has ceramic capacitor between primary circuit and chassis
and between secondary circuit
and chassis. Some withstand voltage tester can generate higher voltage then the capacitor can withstand – so be
careful to set the test voltages as above and no higher – otherwise capacitors may be damaged.
19/24
Withstand Voltage Tester
Withstand Voltage Tester
Withstand Voltage Tester
Withstand Voltage Tester